Generator Requirements for Texas Nursing Homes, Assisted Living and Dialysis Centers

Texas requires emergency generators in nursing facilities, but its 2025 assisted living law (HB 3595) requires a cooled refuge and an outage plan, not a generator. Here is what each facility type must do, how Florida compares, and how families can check.

Texas nursing facilities must have an on-site emergency generator that meets federal and state standards for life support and lighting. Assisted living facilities are not required to own a generator. Since HB 3595 (effective Sept. 1, 2025), they must keep a climate-controlled refuge of at least 15 square feet per resident at 68 to 82 degrees F and report outages longer than 12 hours.

Key facts

  • Texas nursing facilities must supply emergency power for entrances, exits and life support systems with an emergency generator located on the premises (26 TAC 554.1701, citing NFPA 99; 42 CFR 483.90(c)).
  • Federal rule 42 CFR 483.73(e) requires long-term care facilities to implement emergency and standby power systems, with inspection, testing and maintenance, and a fuel plan if they store fuel on site.
  • HB 3595 (89th Legislature, effective Sept. 1, 2025) added Health and Safety Code 247.073. Assisted living facilities had to adopt a power outage plan by Jan. 1, 2026.
  • HB 3595 requires at least 15 square feet per non-bedfast resident in a climate-controlled area of refuge, kept between 68 and 82 degrees F, and notice to the state of an unplanned utility loss of more than 12 hours.
  • HB 3595 does not require a generator. The plan only has to describe the location and type of any on-site generator or other backup power source.
  • HB 3595 tells the state to set construction and licensure standards for backup power, including a generator connection box, for permits issued after Sept. 1, 2026. Compliance is deferred to the later of the first new or renewal license after that date or Jan. 1, 2027.
  • HB 3595 preempts conflicting local rules on assisted living emergency planning. Harris County's fire code amendment, effective Jan. 1, 2025, asked facilities to plan generators that start within three hours of an outage.
  • Florida is stricter: nursing homes and assisted living facilities must keep an alternate power source able to hold indoor temperatures at or below 81 degrees F for at least 96 hours (59A-4.1265 and 59A-36.025).
  • The federal dialysis emergency rule (42 CFR 494.62) requires a plan that covers power failures and annual testing, but the text We reviewed does not itself mandate a generator.
  • Texas DSHS counted 246 Winter Storm Uri deaths, including 19 from carbon monoxide poisoning and 158 from hypothermia.

Quick answer: who has to have a generator in Texas?

The answer depends on the type of facility. The rules are different for nursing homes, assisted living, dialysis clinics and group homes, and they come from different agencies.

Facility typeGenerator required?Main rule
Nursing facility (Medicare and Medicaid certified)Yes, an on-site emergency generator for life support and essential lighting, plus a facility emergency plan42 CFR 483.73 and 483.90; 26 TAC 554.1701, 554.303 and 554.1914
Assisted living facilityNo generator mandate. A climate-controlled area of refuge and a written outage plan are requiredHealth and Safety Code 247.073 (HB 3595); HHSC assisted living rules in 26 TAC chapter 553
Dialysis centerEmergency plan covering power failure, tested every year. We found no explicit generator mandate in the federal text42 CFR 494.62
Group home or small residential settingNot confirmed. Check the facility's license type and the HHSC rules for that licenseVaries by license

This page is general information, not legal advice. If you run a facility, confirm current rule text with the Texas Health and Human Services Commission (HHSC) and your own attorney or compliance consultant. If you are a family member, the checklist near the end of this page tells you what to ask.

Are Texas nursing homes required to have generators?

Yes. Two layers of rules apply to a Texas nursing facility that takes Medicare or Medicaid, and both point to a generator.

The federal layer

The Centers for Medicare and Medicaid Services (CMS) sets the baseline in two places. Section 483.90(c) of Title 42 of the Code of Federal Regulations says an emergency electrical power system must supply power adequate at least for lighting all entrances and exits. It also says that when life support systems are used, the facility must provide emergency electrical power with an emergency generator.

The emergency preparedness rule, 42 CFR 483.73, adds more. Under 483.73(e), the facility must implement emergency and standby power systems. The generator must be located as the Health Care Facilities Code requires. The facility must carry out the inspection, testing and maintenance that code calls for. A facility that keeps fuel on site for its generators must have a plan for that fuel and must keep emergency power running during the emergency unless it evacuates.

Section 483.73(b)(1) also requires policies for the subsistence needs of staff and residents, whether they leave or shelter in place. The list includes food, water, medical and drug supplies, and alternate energy to maintain safe temperatures, emergency lighting, fire detection and alarm systems, and sewage and waste disposal. In plain terms, the federal rule expects a plan for keeping the building safe, not just a generator that turns on.

The Texas layer

Texas licensing rules for nursing facilities repeat the requirement and add detail. Rule 26 TAC 554.1701 says an emergency generator defined in NFPA 99 must be located on the premises where an emergency system must supply power. Rule 26 TAC 554.303, titled Emergency Power, requires emergency power systems to meet NFPA 99 for existing facilities. It requires generators to be installed under NFPA 37 and NFPA 110, with wiring under NFPA 70, the National Electrical Code. It says a generator must be on the premises when a failure could cause major injury or death, and the example it gives is a ventilator failure.

The same rule has practical details:

  • Generators on the outside of the building need a noncombustible protective cover.
  • A generator that runs on public utility natural gas must be able to switch to an alternate fuel source, manually or automatically.
  • Stored fuel must cover at least four hours of required generator operation.
  • Emergency lighting must start automatically within 10 seconds of a normal power interruption.
  • Battery systems must hold for at least one and one-half hours.

Notice what is missing. Four hours of fuel and a generator for life safety loads is a very different standard from Florida's 96 hours of power with temperature control. The Texas rule is built around keeping life support and lights on. It does not, by its own text, require air conditioning to keep running for days. A July 2025 news report from a Houston television station said the same thing in plain language: the 1996 state law requires emergency power for nursing homes, but it does not have to keep heating or cooling running. That is a reporter's summary, so read the rule text before relying on it.

What did Texas change after Winter Storm Uri and Hurricane Beryl?

Winter Storm Uri, February 2021

The Texas Department of State Health Services (DSHS) confirmed 246 deaths related to the winter storm. Of those, 158 were hypothermia and 19 were carbon monoxide poisoning from the misuse of generators, grills, heaters and vehicles. DSHS also described deaths tied to interrupted dialysis or oxygen treatment. More than 4.5 million Texans lost power in the event, according to the federal FERC and NERC report, and ERCOT shed 20,000 megawatts of load at the worst point. Different agencies count deaths differently: the FERC and NERC report says at least 210 people died, while DSHS verified 246. Use the source name when you quote a number.

Hurricane Beryl, July 2024

Beryl made landfall in Matagorda Bay and disrupted electric service for 2.7 million customers, including 2.2 million served by the Houston-area utility, according to the Public Utility Commission of Texas (PUCT) report on the storm. The report says hundreds of nursing and assisted living facilities were affected. It also says the Texas Assisted Living Association reported that its members had trouble getting information from the utility, with staff waiting hours on customer service lines.

Assisted living was where the policy gap showed. A nursing facility already had a generator rule. An assisted living facility did not. After Beryl, the Harris County Commissioners Court approved a fire code amendment, effective Jan. 1, 2025. The county's own page says assisted living and similar facilities "must develop a plan to install generators that activate within three hours of a power outage." News outlets reported different compliance dates for the county rule, and We could not confirm which is official, so a Harris County facility should ask the Fire Marshal's office directly.

The 2025 state law

The Legislature answered with House Bill 3595, which took effect Sept. 1, 2025. The next sections explain what it does. The important point is that it does not require a generator. It also says that, to the extent of any conflict, it and the rules under it preempt and supersede local rules on emergency planning for assisted living residents. A Houston news report from July 2025 raised the question of whether that language makes the county's generator requirement moot. That question is for a lawyer or the county, not for a news site to settle.

Do Texas assisted living facilities need backup power? What HB 3595 requires

There is no Texas law that says an assisted living facility must own a generator. Several 2025 bills would have required one, but the law that passed is narrower. HB 3595 added Section 247.073 to the Health and Safety Code. The agency it names is the commission (HHSC).

The outage plan

Each facility had to adopt and implement an emergency preparedness and contingency operations plan by Jan. 1, 2026. In a power outage, the plan must provide:

  • For each resident who is not bedfast, a climate-controlled area of refuge with at least 15 square feet per resident.
  • For bedfast residents, a climate-controlled room.
  • Notice to HHSC of an unplanned interruption or loss of electric utility service for more than 12 hours.

The plan must keep each refuge area and each bedfast resident's room between 68 and 82 degrees Fahrenheit. The Texas Assisted Living Association's summary adds that, if the refuge cannot stay in that range, residents should be moved out.

What the plan must say about generators

The plan must include information on building equipment, including "the location of and type of on-site generator equipment or backup power source," if any. So a facility with no generator can comply on paper by describing what it does use: batteries, a contract for a mobile unit, a cooling center arrangement, or an evacuation plan. The law does not say how long that backup has to last.

What comes later

The law also tells HHSC to set construction and licensure standards that cover backup power, including a generator connection box, for permits issued after Sept. 1, 2026. A connection box is a wall-mounted inlet that lets a portable or rented generator plug into the building safely. Compliance with those standards is deferred to the later of the first new or renewal license issued on or after Sept. 1, 2026, or Jan. 1, 2027. The Texas Assisted Living Association's page warns that HHSC rulemaking will likely take longer than the statutory deadlines. We could not confirm whether HHSC has adopted final standards, so a new facility should check the current Texas Administrative Code.

Family access to the plan

Under the statute, a facility must give HHSC its plan on request, in the form the agency prescribes. A facility must also give a resident or family member a summary of the plan on request. That is the legal hook for the checklist at the bottom of this page.

Which rule section holds the details

The Texas Assisted Living Association points to 26 TAC 553.275 as the rule section for emergency preparedness and says HHSC published an Assisted Living Facilities Emergency Preparedness Checklist. Texas rule numbers sometimes move during rewrites, and a proposal that would renumber this rule has been published. Confirm the current number on the Texas Administrative Code before you cite it.

How do CMS emergency preparedness rules apply to generators?

The CMS Emergency Preparedness Rule applies to Medicare and Medicaid participating providers. It has four core parts: a risk assessment and plan, policies and procedures, a communication plan, and training and testing. Long-term care facilities find their version at 42 CFR 483.73 and dialysis facilities at 42 CFR 494.62.

Nursing facilities

The nursing facility version is the more detailed. Beyond the power system in 483.73(e), it requires the facility to track the location of on-duty staff and sheltered residents. If it relocates people, it must record the name and location of the receiving site. It requires exercises to test the plan at least twice per year, including unannounced staff drills.

For Texas facilities, the state rule on emergency preparedness, 26 TAC 554.1914, adds its own list. The plan must include a risk assessment, a description of the resident population and eight core functions: direction and control, warning, communication, sheltering, evacuation, transportation, health and medical needs, and resource management. Facilities must run one unannounced annual drill with staff for severe weather and other likely emergencies. They must train new staff within 30 days and review the plan at least once a year and within 30 days after an emergency or remodel. If a facility decides to evacuate, it must notify the local emergency management coordinator and the HHSC regional office.

That rule does not itself set energy source requirements. The generator details sit in the physical environment and emergency power rules described above.

Dialysis centers

Dialysis facilities follow 42 CFR 494.62. The text We reviewed requires strategies for emergencies identified in a risk assessment, including power failures, an emergency communication plan, and testing of the plan at least annually. We did not find a sentence that requires a generator. In practice, a clinic needs a plan for finishing or safely stopping treatments when power is lost, and many arrange backup power or transfer agreements. Ask the clinic what it does, and see the dialysis section of our medical needs guide for patients who dialyze at home.

Do dialysis centers need generators in Texas?

The federal rule does not use the word generator in the passage We reviewed, but it does require planning for power loss. Texas licensing for dialysis facilities is a separate set of rules that We did not verify here. If you are a dialysis patient, treat the question as one to put to the clinic directly.

Good questions to ask a center:

  1. If the power fails in the middle of my treatment, what happens?
  2. Do you have a generator on site, or a contract for a mobile one?
  3. Do you have a transfer agreement with another center? Where would I go?
  4. How will you contact me during an outage if phones are down?
  5. Do you have a plan for reduced treatments or a modified diet and fluid plan if the center is closed for several days?

The PUCT's Beryl report shows the Houston-area utility's priority list for its mobile emergency generation units. Hospitals were first, senior and assisted living was fourth, and small emergency rooms and dialysis clinics were fifth. The report also says no specific customers or locations were identified in advance, which slowed deployment. Being on a priority list helps but does not guarantee power. The PUCT customer rule on critical care designations says outright that a designation does not guarantee an uninterrupted supply of electricity.

What does HHSC require for emergency power and temperature during an outage?

HHSC is the state agency that licenses nursing facilities and assisted living facilities in Texas. The rules above are the ones it enforces. Here is a plain summary of the power and temperature expectations.

ItemNursing facilityAssisted living facility
Generator on siteRequired for life support and lighting loadsNot required; plan must describe any generator or other backup source
Temperature standardNo fixed number found in 554.1701 or 554.303; federal rule requires alternate energy to maintain safe temperatures in the subsistence plan68 to 82 degrees F in each refuge area and bedfast room
SpaceNo square-foot figure found15 square feet per non-bedfast resident in a refuge area
FuelStored fuel for at least four hours of required generator operation (554.303)No fuel minimum in the statute
Outage reportingReport evacuation decisions to HHSC and local emergency management (554.1914)Report unplanned utility loss longer than 12 hours
Plan deadlineExisting requirementJan. 1, 2026

HHSC surveyors may ask to see an assisted living facility's plan and can cite deficiencies. The statute lets the agency assess penalties under Subchapter C against facilities that violate the section.

Nursing facilities also register with the Texas Information and Referral Network under Health and Safety Code 242.0395. This helps the state identify people who need help if an area is evacuated for a disaster. Separately, Texas keeps trust funds that can pay for emergency assistance to a nursing home or assisted living facility to relieve an immediate threat to residents, such as when a court appoints a trustee.

How Texas compares to Florida

Florida wrote a hard runtime and temperature standard after Hurricane Irma in 2017. Its rule for nursing homes (59A-4.1265) and for assisted living facilities (59A-36.025) both require an alternate power source that can keep indoor temperatures at or below 81 degrees F for at least 96 hours after the loss of primary power. The nursing home rule was first adopted March 26, 2018 and amended effective Jan. 25, 2026. The assisted living rule began as 58A-5.036 and moved to 59A-36.025 on July 1, 2019, so older articles use the old number.

ItemTexasFlorida
Nursing home generatorYes, for life support and lighting; four hours of stored fuel under 26 TAC 554.303Yes, alternate power for at least 96 hours with indoor air at or below 81 degrees F
Assisted living generatorNot required; refuge and plan requiredRequired alternate power for 96 hours at or below 81 degrees F
Cooled space per resident15 sq ft per non-bedfast resident (assisted living)30 sq ft (nursing home); 20 sq ft (assisted living, using 80% of licensed beds)
Fuel on siteAt least four hours for nursing homesNursing homes 72 hours on site and 96 hours in a declared emergency; assisted living 48 hours (16 or fewer beds) or 72 hours (17 or more), 96 hours in a declared emergency
Who reviews the planHHSC on requestCounty emergency management agency approves; proof sent to the state agency within 30 days

The two states agree on one thing: neither promises that a power-hungry facility never loses power. They both plan for the worst. The gap is how long and how cool. Florida requires an assisted living facility to have power for four days at a set temperature. In Texas, the same setting must have a plan and a cooled room, and the law does not set a runtime. See our Florida nursing home and ALF rule guide for the full Florida side.

Do Texas group homes and small residential settings need generators?

We could not confirm a statewide generator mandate for group homes, home and community-based settings or adult day programs. Those settings are licensed or certified under different HHSC rules than nursing and assisted living facilities. If you operate one, find the exact license type on your certificate, read the rule chapter for that license, and ask HHSC in writing whether backup power is required. If you are a family member, ask the operator for the written emergency plan and what the plan says about power.

For any small setting where a resident depends on oxygen concentrators, ventilators or refrigerated medicine, the practical standard is higher than the legal minimum. A plan that says "call the utility" is not a plan. See the medical needs guide for the PUCT critical care designation and what it does not promise.

How to check a Texas facility's emergency plan

You can learn a lot before you move a loved one. Here is a practical order of steps.

  1. Look up the license. HHSC runs a public provider search where you can check a facility's license status and inspection history. Third-party guides point to it as TULIP at tulip.hhs.texas.gov. Confirm the address on the HHSC website before you enter personal details.
  2. Ask for the summary. For an assisted living facility, HB 3595 says the facility must give a resident or family member a summary of its emergency plan on request. Ask in writing and keep a copy.
  3. Ask four questions about power. Do you have a generator? What does it run? How many hours of fuel are on site? Is there a cooled area big enough for every resident?
  4. Ask about the connection box. If there is no generator, is there a connection box and a contract for a mobile one? Who delivers it and how fast?
  5. Ask about the last test. When was the generator last run under load, and who inspected it? Nursing facilities must follow NFPA inspection, testing and maintenance requirements under the federal rule.
  6. Ask about evacuation. Where do residents go, who transports them, and how are families told?
  7. Report concerns. If a facility will not share a plan summary or you see a hazard, contact HHSC Long-Term Care Regulation through the HHSC website, or the state long-term care ombudsman.

A facility that answers all of this quickly and in writing is usually one that has thought about it.

What nursing home and assisted living administrators should do now

If you run a facility, the rules mean concrete work. This list is general and does not replace advice from your compliance counsel.

  • Confirm the plan was adopted and implemented by Jan. 1, 2026 if you run an assisted living facility, and keep dated proof of staff training and drills.
  • Measure your refuge. Multiply your non-bedfast resident count by 15 square feet and compare it to the cooled space you can actually hold at 68 to 82 degrees F on a 100 degree day or a freezing night.
  • Write down the generator or backup source. The plan must say where it is and what type. If it is a rental contract, keep the contract and the delivery time guarantee with the plan.
  • Put a connection box in the plan for any renovation or new build. The state is directed to set standards for permits issued after Sept. 1, 2026.
  • Set outage reporting in the call tree. Someone must know who calls HHSC when the utility loss crosses 12 hours.
  • Test under load. Nursing facilities must follow the NFPA inspection and testing requirements in the federal rule. A generator that starts but cannot carry the cooling load is a risk even if the paperwork is in order. See the commercial generator code guide.
  • Plan fuel. Texas sets only four hours of stored fuel for nursing facilities, but a storm may last days. Pick a target you can defend and contract for delivery before the storm.

Texas sets no fixed runtime for assisted living. If you want a defensible internal standard, Florida's 96 hours is a useful benchmark, but it is not Texas law.

How to choose a provider

  • Look up the facility's license type and inspection history on the HHSC provider search.
  • Ask in writing for the emergency plan summary (assisted living facilities must provide it on request under HB 3595).
  • Ask whether there is a generator, what fuel it uses, and how many hours of fuel are stored on site.
  • Ask for the size of the cooled area of refuge and whether it covers every non-bedfast resident at 15 square feet each.
  • Ask what temperature range the building holds in an outage (the state range is 68 to 82 degrees F in assisted living).
  • Ask who calls HHSC when an outage passes 12 hours and how families are told.
  • Ask when the generator was last tested under load and who inspected it.
  • Ask where residents would go if the building must be evacuated and how they would be moved.
  • For a dialysis patient, ask the center what happens if power fails mid-treatment and which center is the backup.
  • Confirm current rule text and numbering on the Texas Administrative Code before relying on any citation here.

Related standby generator installation guides

Standby generator installation by state and city

Questions people ask

Are Texas nursing homes required to have generators?

Yes. Federal rule 42 CFR 483.90(c) and Texas rule 26 TAC 554.1701 require an emergency generator on the premises when life support systems are used, and the Texas rule 554.303 sets installation, fuel and protection details. The standard focuses on life support and essential lighting, not on keeping the whole building cool for days. Ask any facility how its generator would handle cooling.

Do Texas assisted living facilities have to have a generator?

No. HB 3595, effective Sept. 1, 2025, requires an outage plan, a climate-controlled area of refuge of at least 15 square feet per non-bedfast resident, a 68 to 82 degree F range, and notice to HHSC of an outage longer than 12 hours. The plan only has to say where any generator or backup source is and what type it is.

What did Texas change after Hurricane Beryl?

The Legislature passed HB 3595 in 2025, which created the assisted living outage plan and refuge requirement and told HHSC to write backup power construction standards, including a generator connection box, for permits after Sept. 1, 2026. Harris County separately adopted a fire code amendment effective Jan. 1, 2025. HB 3595 says it preempts conflicting local rules.

What is a generator connection box?

It is a fixed inlet on the outside of a building, wired to the electrical system through the proper switching, so a mobile generator can be plugged in quickly and safely. It avoids unsafe improvised hookups. HB 3595 directs the state to include one in backup power standards for new assisted living permits after Sept. 1, 2026.

How do I get a Texas facility's emergency plan?

For an assisted living facility, state law says the facility must give a resident or family member a summary of the plan on request. Ask in writing. HHSC can also request the plan from the facility. For nursing facilities, ask the administrator and review the facility's inspection history on the HHSC provider search.

Does a critical care designation keep my power on?

No. PUCT rule 25.497(c)(4) says a critical care or critical load designation does not guarantee an uninterrupted supply of electricity. It brings notice and disconnection protections. A person who depends on a powered medical device still needs their own backup plan, such as a generator, battery or a place to go.

How does Texas compare to Florida for care facility generators?

Florida requires nursing homes and assisted living facilities to hold indoor temperatures at or below 81 degrees F for at least 96 hours, with fuel on site. Texas requires a nursing home generator for life safety loads and, for assisted living, a refuge and a plan. Florida's rule is more specific about duration and cooling.

Where do I report a care facility that is unsafe in an outage?

Contact HHSC Long-Term Care Regulation through the HHSC website, which lists how to file a complaint about a licensed facility. In an immediate emergency, call 911. The state long-term care ombudsman, a separate office, can also help residents and families with concerns, and you can ask about both offices on the HHSC site.

Sources

This guide was written by our editorial team from the public sources listed above. It is general information, not legal advice; confirm licensing and terms directly with any provider.

New ebook from The Company ChronicleHow to Research Like a Wall Street AnalystFind original sources, analyze trends, and build your own insights. 36 pages with worksheets.Get the ebook · $29Instant PDF download

Business Spotlight

Want us to publish your business?

Our team writes and publishes articles about your business on The Company Chronicle every month, with a link to your website. Plans from $30 a month, cancel anytime.

Publish with us

The Chronicle directory

What are you into?

The Chronicle, coast to coast

Every corner has a story.

The full Chronicle illustration