How to Connect a Portable Generator to Your House Legally: Inlets, Interlocks and Manual Transfer Switches

What a power inlet, a breaker interlock and a manual transfer switch do, which electrical code applies in Texas (2026 NEC) and Florida, who may do the work, and how neutral bonding and load limits affect a portable setup.

To connect a portable generator to a house legally, have a licensed electrician install an outdoor power inlet with either a breaker interlock listed for your panel or a manual transfer switch, and get the permit your city or county requires. Texas has enforced the 2026 NEC since September 1, 2026; Florida still uses the 2020 NEC. Never backfeed through a wall outlet.

Key facts

  • Texas adopted the 2026 NEC as the state electrical code effective September 1, 2026 (16 TAC 73.100; 51 TexReg 5776). Pages that still cite the 2023 NEC for Texas are out of date.
  • Florida's Building Code 8th Edition (2023) uses the 2020 NEC; the 9th Edition, based on the 2023 NEC, takes effect December 31, 2026 per Florida Statute 553.73(7)(e), though Tampa announced January 1, 2027.
  • A UL explainer says breaker interlock kits are treated as part of a panelboard under ANSI/UL 67, usable as transfer equipment when covered by the panel's listing for a specific kit; transfer switches are evaluated to UL 1008.
  • A summary of the 2023 NEC says a portable generator inlet must be located outside the building, and inlets rated 100 amps or more need an interlocked disconnecting means unless rated as a disconnect.
  • Inlet boxes come in 30 or 50 amp versions, typically NEMA L14-30 or 14-50; at 240 volts that is a ceiling of 7,200 and 12,000 watts by our arithmetic.
  • Texas SB 1252 (2025) limits city regulation of residential backup systems of up to 50 kW, but TDLR says licensed Texas electrical contractors must still do non-exempt work to the NEC.
  • Texas SB 1202 (2025, Local Gov't Code 247.0025) lets a licensed inspector or master electrician review home backup power as a third party, with city approval due within three business days after notice.
  • Florida 489.503(6) lets an owner do electrical work on their own single-family or duplex home, but the owner must personally appear and sign the permit application.
  • A national 2026 cost guide lists portable generator with transfer switch hookup at $990 to $2,909 (average $1,693).

The short version: the legal ways to connect a portable generator

There are only a few safe ways to get portable generator power into a house. Which one is legal in your city depends on the electrical code your area enforces and on who inspects the work.

MethodWhat it doesElectrical work?Main limit
Extension cords to appliancesPower a few items directlyNoReaches only what the cords reach. No furnace, well pump or hard-wired loads.
Power inlet plus breaker interlockFeeds the main panel through a locked-out breaker so the house and the utility cannot be connected at onceYes, licensedYou choose which circuits to run. You must watch the load yourself.
Power inlet plus manual transfer switchMoves a chosen group of circuits to the generatorYes, licensedOnly the circuits wired to the switch
Plugging the generator into a wall outlet ("backfeeding")None legitimateNot allowedCPSC and OSHA both warn against it

Backfeeding is dangerous because it can electrocute lineworkers and neighbors on the same transformer. CPSC says never to power house wiring by plugging a generator into a wall outlet, and OSHA says portable generators should be used as standalone power sources unless connected through properly wired by-pass or isolation connections. Read backfeeding and portable generator safety for the full explanation.

This page is general information, not legal or electrical advice. The details of your panel, your generator and your city decide what is allowed. A licensed electrician and your local inspector have the final say.

Which electrical code applies? Texas 2026 NEC and Florida

Texas: the 2026 National Electrical Code since September 1, 2026

The Texas Department of Licensing and Regulation (TDLR) amended 16 Texas Administrative Code 73.100 to adopt the 2026 National Electrical Code (NEC) as the state electrical code, with a limited exception for ground-fault protection on certain outdoor outlets. TDLR says the adoption was published in the August 28, 2026 Texas Register (51 TexReg 5776) and took effect on September 1, 2026. TDLR's Texas Circuit bulletin (July 30, 2026) says that starting September 1, all non-exempt electrical work in Texas, whether in a city or in the county, must follow the 2026 NEC, and that state electrician exams moved to the 2026 NEC on the same date. The City of Houston says permit applications submitted on or after September 1, 2026 are reviewed under the new state minimum code.

Be careful with older web pages. Several copies of the Texas rule and a TDLR guide page still say the state adopted the 2023 NEC effective September 1, 2023. That was the rule before the 2026 update. When a page cites the 2023 edition for Texas work today, it is out of date.

TDLR's inspectors also say a city may amend the state code but may not adopt a code below the state minimum. That is TDLR's reading, and a city may have its own amendments, so ask your building department what it enforces. We could not load the Dallas or San Antonio code pages, so we do not describe their local amendments here.

Florida: Florida Building Code and the 2020 NEC, with a change coming

Florida's building code is set by the Florida Building Commission. Charlotte County's building code page lists the Florida Building Code, 8th Edition (2023) and the 2020 NEC as effective December 31, 2023 to the present. The 9th Edition (2026) is based on the 2023 NEC and becomes effective December 31, 2026 under Florida Statute 553.73(7)(e), according to the Commission's training materials. The City of Tampa has announced that the 9th Edition goes into effect January 1, 2027, and that projects must have a permit application accepted by December 31, 2026 to vest under the 8th Edition. These dates conflict by one day, so confirm which edition your permit will be reviewed under with your county or city. In practice, a permit application filed before the changeover is reviewed under the old edition, and one filed after is reviewed under the new one.

That means Florida and Texas apply different NEC editions right now: Florida's 2020 NEC (moving to the 2023 NEC), and Texas's 2026 NEC.

What do the code rules say about inlets and transfer equipment?

The NEC is a copyrighted code, and we could not load the 2026 text for this guide. What follows comes from published summaries and a UL explainer. Treat the section numbers as a map, not a quote, and ask your electrician or inspector to confirm them against the 2026 NEC for a Texas job.

Transfer equipment (Article 702, optional standby systems)

Article 702 covers optional standby systems, which is the code home for a portable generator connected to a house. A UL explainer published by IAEI in 2017 says NEC 702.5 requires transfer equipment to be suitable for the intended use and designed and installed to prevent inadvertent interconnection of the normal and alternate sources. In plain words: the house must never be connected to the utility and the generator at the same moment, because that sends power backward onto the grid.

Are interlock kits legal?

This is the question people most often ask, and the honest answer is "usually, but your inspector decides." The same UL explainer says breaker interlock kits are treated as part of a panelboard, are investigated for compliance with the panelboard standard ANSI/UL 67, and can be used as transfer equipment in optional standby systems, including with portable generators. Transfer switches, by contrast, are evaluated to UL 1008. The explainer says a kit may be factory or field installed when it is covered by the listing of a particular panelboard, and that the panel is marked to identify the specific kit it may use.

What this means for a buyer:

  • Use the interlock kit that the panel maker identifies for your exact panel model. A generic kit that "fits" is not the same as a listed combination.
  • Look for the panel marking that refers to Article 702 and the kit.
  • Ask the inspector in advance whether the interlock will be accepted. Some trade discussions say the 2020 and 2023 text does not name interlocks, and others say a proposal to add them for the 2026 edition was submitted. We could not confirm what the 2026 text says, so this is the single most important thing to verify with your local authority.

Inlet location and disconnect

Per a summary of the 2023 NEC from a code-training provider, section 702.12 includes these rules for portable generators:

  • For a portable generator of 15 kW or less connected with a flanged inlet or other cord-and-plug connection, a separate disconnecting means is not required where the ungrounded conductors serve or pass through a building.
  • New in 2023: the flanged inlet or other cord-and-plug connection must be located outside the building or structure.
  • For power inlets rated 100 amps or more, the equipment must be listed for its use, and inlets that are not rated as a disconnecting means must have an interlocked disconnecting means.

Residential portable generator inlets are normally 30 or 50 amps, so the 100 amp rule is for larger installations. The outdoor-location rule matters for homes: an inlet on the exterior wall, not in the garage.

Signs

An example county sheet from Florida, written to the 2008 NEC and now out of date, requires a sign at the service equipment that tells the type and location of on-site optional standby power sources, and a manufacturer's installation information kept on site for inspection. The details of signs have changed across NEC editions, so ask your inspector which sign wording the current edition requires.

What is a generator inlet box, and which size do I need?

A generator inlet (also called a power inlet box) is a weatherproof outdoor receptacle, mounted on the outside wall near the panel, that you plug the generator's cord into. It is wired to the panel by an electrician. It lets you connect without running cords through doors and windows, which keeps the generator outside, away from openings.

A generator maker's hookup guide says inlet boxes come in 30 or 50 amp versions, usually using NEMA L14-30 or 14-50 plugs. We could not confirm other plug types such as CS6365 in a source we loaded, so match the inlet, the cord and the generator outlet by their printed ratings and shapes.

The amp and watt math

Watts equal volts times amps, the same formula manufacturers publish for appliances. For a 240 volt connection:

InletAmpsMaximum watts (240 V times amps)What it means
30 amp307,200A 7,500 or 12,000 watt generator will be limited by the inlet and cord, not by the engine
50 amp5012,000Uses a larger cord and a generator with a matching outlet

These are our calculations of the electrical ceiling. Real safe limits are lower, because breakers, wire and cord ratings and continuous-load rules reduce what you should draw. Never pick an inlet bigger than the generator outlet or the wire the electrician installs. The generator's own outlet and breaker size set what it can feed.

Cords

CPSC advises heavy-duty, outdoor-rated cords with a wattage rating that exceeds the load, with all three prongs and no cuts. For inlet connections, use the cord set the generator and inlet makers list for that amperage. We do not give a wire gauge because the right size depends on current and length, and we did not load a table; the cord's printed rating and the inlet manufacturer's instructions decide.

Manual transfer switch or interlock: which is better?

QuestionInterlock kit with inletManual transfer switch with inlet
Which circuits can I power?Any circuit in the main panel, one breaker at a time (per a generator maker's guide)A preset group, such as the refrigerator, furnace fan or sump pump
Who controls the load?You do, by choosing which breakers to switch onThe switch limits you to the wired circuits
CostGenerally the lower cost option, per the same guideHigher: a national guide lists transfer switch installs at $829 to $2,652 (Homeyou, Sept. 2026)
Risk of overloadHigher. It is easy to switch on too many breakers.Lower, because the circuits are chosen in advance
Code statusAccepted when the kit is listed for the specific panel and your inspector agreesTransfer switches are evaluated to UL 1008
Neutral handlingNeutral stays connectedSome switches also switch the neutral (see below)

For a home that wants a few circuits and plans to run a generator seldom, an interlock is the flexible choice. For a home where the family may not remember the procedure in the dark, a manual transfer switch is more forgiving. Neither is automatic, and neither replaces a standby generator with an automatic transfer switch. See automatic transfer switches.

How the interlock is used: order of operations

An installer will label the panel with the exact steps for your equipment. In general, the sequence works like this. Follow the label on your own panel, not this list:

  1. Place the generator outdoors, far from windows, doors and vents (CPSC and CDC say 20 feet or more for portable units), on a dry surface under an open canopy.
  2. With nothing plugged in, start the generator and let it settle.
  3. Plug the generator cord into the generator, then into the inlet.
  4. At the panel, turn off the main breaker. This disconnects the house from the utility.
  5. Slide the interlock plate so that the generator breaker can be turned on. The plate is designed to block the main from turning on at the same time.
  6. Turn on the generator breaker.
  7. Add branch circuit breakers one at a time, largest motor loads first, and watch the generator.
  8. Leave off the loads you do not need, especially 240 volt appliances.

To return to utility power, reverse the steps: turn off the branch circuits, turn off the generator breaker, shut the generator down, unplug it, slide the interlock back, and turn the main breaker on when utility power is restored. If your utility power is out, do not switch the main back on by habit. Check that the lights outside are back on first. After a storm, FPL says homeowners own and must repair storm damage to the service stack, attachment hardware, riser and meter box before power can be restored. A damaged meter or mast needs an electrician and a utility check.

Neutral bonding, floating neutral and GFCI tripping

This is the area where good installers disagree with online posts, so read it carefully. We could not load the NEC grounding text, and the explanations below come from trade and manufacturer-style discussions, so confirm with the generator maker's manual, the transfer equipment instructions and your inspector.

The idea

In a home's wiring, the neutral wire is connected to the ground at exactly one point, in the service equipment. A portable generator, depending on its design, may have its neutral either bonded to the frame (tied to ground inside the generator) or floating (not tied). If the neutral gets bonded in more than one place, the electricity can take a path that fools safety devices.

Why it matters

  • With a bonded generator feeding a transfer switch that does not switch the neutral, there can be two neutral-to-ground connections, one in the generator and one in the house panel. Explanations say the extra path can send current where it should not go, and can cause a ground-fault device (GFCI) on the generator to trip.
  • With a transfer device that does switch the neutral (often called a three-pole or switched-neutral design), the generator's neutral bond can be the only one while the generator runs.
  • With a floating-neutral generator on a non-switching transfer device, the house panel's bond is the only one. Some trade discussions note risks with a floating generator and switched neutral, because that setup has no ground reference.

Which setup is right depends on both the generator and the transfer equipment. The generator manual should say whether the neutral is bonded, and whether it can be floated or bonded by a plug or screw. The interlock or transfer equipment instructions should say whether the neutral is switched. Do not remove a bonding screw or plug on your own to stop tripping. If the installer cannot tell you which type you have and what the manual allows, stop and get the answers in writing.

OSHA's construction rule 29 CFR 1926.404(f)(3)(i) is a different situation (a job site generator that only supplies its own receptacles), but it shows that bonding of the generator's frame and equipment ground terminals is a deliberate design choice, not an accident.

Can I power my whole house, or run my AC, with a portable generator?

Usually no for the whole house, and rarely for central air. Two limits apply: the generator's running watts and the inlet's amps.

  • A 30 amp inlet has a ceiling of about 7,200 watts at 240 volts by our math, and the safe sustained number is lower.
  • A manufacturer's sizing guide lists a 3 ton central air conditioner at 3,000 to 3,500 running watts and 5,000 to 6,000 starting watts. With other loads, that is more than many portable generators and cords can deliver. See our sizing examples in the portable generator buying guide.
  • A window air conditioner (900 to 1,200 running, 1,800 to 2,400 starting watts in the same guide) is a more realistic target for a 7,500 watt unit.

If you want automatic whole-house power, the right tool is a standby generator. See whole house vs essential circuits and generator for central AC.

Load management on a portable setup

  • Make a card for the panel door listing "essential" breakers: refrigerator, freezer, furnace fan, some lights, internet, a window unit.
  • Start the biggest motor loads first and one at a time.
  • Leave 240 volt loads (dryer, electric range, water heater, central AC) off unless the generator and inlet are sized for them.
  • Watch for the generator slowing, the lights dimming or the generator breaker tripping, and shed a load before it trips.
  • Do not let family members "help" by turning breakers on. A written procedure by the panel prevents mistakes.

What about meter collar adapters?

A meter collar adapter sits between the utility meter and the meter socket and has a place to plug in a generator. They are sold as an alternative to an inlet. We did not find a code section, Texas or Florida agency page, or utility policy in the sources we loaded that approves their use on a home with a portable generator. Whether one is allowed depends on the utility that owns the meter and on the local inspector. Call your electric utility and your building department, and get the answer in writing before buying one. A device that interrupts the utility's connection is work on utility-owned equipment in many places, and breaking a utility seal can have its own consequences. Do not remove or open a meter yourself.

Permits and licensing in Texas

  • License required. Texas Occupations Code 1305.151 says a person or business may not perform or offer electrical work unless licensed under chapter 1305, except as exempted in 1305.003. TDLR says non-exempt electrical work must be done by licensed electrical contractors using licensed electricians.
  • Homeowner exemption. Section 1305.003(a)(6) exempts work, not specifically regulated by a municipal ordinance, performed in or on a dwelling by a person who owns and lives in the dwelling. Many large cities regulate this by ordinance and may require a permit or limit owner wiring, so confirm with your city first. Even where an owner may legally do the work, the work must still meet the 2026 NEC.
  • Permit. Houston's permitting center, for example, reviews electrical permit applications under the 2026 NEC for applications submitted on or after September 1, 2026. Call the electrical inspections team at 832-394-8860 for Houston questions.
  • SB 1252 (2025). This law bars Texas cities from adopting or enforcing rules that regulate the installation or inspection of a "residential energy backup system," defined as a backup energy system at a residence providing no more than 50 kW or with storage of no more than 100 kWh. It took effect September 1, 2025. TDLR says that even under SB 1252, non-exempt electrical work on these systems must still follow chapter 1305 and the NEC and be done by licensed Texas electrical contractors. Municipally owned utilities, such as Austin Energy and CPS Energy, keep their authority within their service areas. Do not read SB 1252 as "no permit and no electrician needed." Confirm the permit step with your city or county. See Texas permits.
  • SB 1202 (2025). This added Local Government Code 247.0025 for a "home backup power installation" serving a one- or two-family dwelling at 600 volts or less. A licensed electrical inspector or Texas-licensed master electrician, among others, may review plans and inspect as a third party. The city must issue its approval, permit or certification within three business days after it receives notice that the third party approved the work, and construction may begin once that notice is submitted. If a city has not posted its rules and fee schedule, it may not charge a fee for the approval. Whether this route applies to a simple inlet job is a question for your electrician and city.

Master electrician requirements, for context: 12,000 hours of on-the-job training under a master and two years as a journeyman (application fee $45); a journeyman needs 8,000 hours (fee $30). Verify any license on TDLR's license lookup before work begins. See Texas installer licensing.

Permits and licensing in Florida

  • Electrical contractors. Florida 489.505 defines electrical contracting as installing, repairing or altering electrical wiring and apparatus. A certified electrical contractor holds a Department of Business and Professional Regulation (DBPR) certificate of competency and may work statewide. Check a license on the DBPR license lookup.
  • Owner exemption. Florida 489.503(6) lets an owner act as his or her own electrical contractor on a single-family or duplex residence for the owner's own use, not for sale or lease. The owner must personally appear and sign the permit application, and the exemption does not cover anyone the owner hires. Selling or leasing more than one structure within a year after completion is evidence the work was for sale or lease.
  • Local permit and inspection. Florida 489.537(3) preserves the authority of counties and cities to regulate electrical work through permits, fees and inspections, and to require plan approval before work begins. Permit rules vary by county. Ask the building department in Miami-Dade, Hillsborough, Orange or Duval about inlet or interlock work.

See Florida permits and Florida installer licensing. Florida also treats gas piping for a generator as licensed plumbing or LP gas work, which is separate from the electrical hookup of a portable generator.

How much does a generator inlet install cost?

No agency sets these prices, and we found no Texas-only or Florida-only figure in a named, dated source. The published national numbers are:

ItemRangeSource and year
Portable generator with transfer switch hookup$990 to $2,909 (average $1,693)Homeyou, updated Sept. 2026
Transfer switch install$829 to $2,652Homeyou, Sept. 2026
Generator permitsUsually $50 to $200Inch Calculator, 2023
Sub-panel to connect a generatorAbout $500 to $2,000Inch Calculator, 2023
Electrician labor$50 to $200 per hourInch Calculator, 2023

The Homeyou guide says labor time depends on panel access, the distance to the generator inlet and whether new outdoor receptacles or conduit are needed, and that permits and inspections may add to the price. For context on wages, the U.S. Department of Labor's O*NET reports that Texas electricians earned a median of $58,570 in 2025 and Florida electricians $57,250. Those are wages paid to workers, not what a customer is charged. Get at least two written quotes that name the inlet amperage, the interlock or switch model, the permit and the inspection.

Before and after: a safety checklist for the first use

  • Install battery-powered CO alarms on every level and near sleeping areas. CPSC advises alarms certified to UL 2034, IAS 6-96 or CSA 6.19.01 and tests each month.
  • Place the generator on a dry surface, outdoors, 20 feet or more from doors, windows and vents.
  • Never run the generator in a garage or shed, even with the door open. NIST testing cited by CPSC found dangerous CO levels indoors with a garage door fully open.
  • Turn off and cool the generator before you refuel. Store fuel outside living areas in labeled, non-glass containers.
  • Keep a copy of the panel label, the interlock instructions, the manual and the permit in a folder.
  • Test the setup before an outage, in daylight, with a helper.

Florida's Irma data show why this matters: generator use caused 97.5 percent of the Irma-related CO exposures identified by the Florida Department of Health, and 62.8 percent of 516 generator-related exposures involved homes with no CO detector. In Texas, DSHS counted 19 CO deaths among the 246 Winter Storm Uri deaths it confirmed.

How to choose a provider

  • Decide first whether cords are enough or whether you need a permanent connection.
  • Confirm which NEC edition your city or county will review under (Texas: 2026; Florida: 2020, changing at the 9th Edition).
  • Hire a licensed electrician (TDLR in Texas, DBPR in Florida) unless you qualify for and choose the owner exemption.
  • Use an interlock kit that the panel maker lists for your exact panel model.
  • Ask the inspector, before buying, whether the interlock or manual transfer switch will be accepted.
  • Choose a 30 or 50 amp outdoor inlet that matches the generator outlet and cord.
  • Confirm in writing whether the generator's neutral is bonded or floating and what the transfer equipment requires.
  • Mount the inlet on the outside wall of the building.
  • Post a printed operating procedure and a list of essential breakers at the panel.
  • Test in daylight: start the generator, main OFF, interlock slide, generator breaker, then add circuits one at a time.
  • Keep CO alarms working and the generator outdoors, 20 feet from openings.
  • Never plug a generator into a wall outlet.

Related standby generator installation guides

Standby generator installation by state and city

Questions people ask

How do I safely connect a portable generator to my house?

Use a licensed electrician to install a listed power inlet and either a breaker interlock made for your panel or a manual transfer switch. Either one stops the house and utility from being connected at the same time. Run the generator outdoors, 20 feet from openings. Never plug it into a wall outlet. CPSC and OSHA warn that backfeeding can electrocute lineworkers and neighbors.

What is a generator inlet box?

It is a weatherproof outdoor receptacle that is wired to your panel so you can plug the generator cord into the house safely. Inlet boxes come in 30 or 50 amp versions, usually with NEMA L14-30 or 14-50 plugs per one maker's guide. Under a 2023 NEC summary, the inlet must be located outside the building. Match the inlet, cord and generator outlet by their rated amperage.

What is a breaker interlock kit and is it legal?

An interlock kit is a plate on the main panel that stops the main breaker and generator breaker from being on at the same time. UL says interlock kits are part of a listed panelboard under ANSI/UL 67 and can serve as transfer equipment when the panel is marked for that kit. Whether your inspector accepts one is a local decision, so ask before you buy.

Manual transfer switch vs interlock: which is better?

An interlock lets you power any circuit in the panel, one breaker at a time, and costs less, but it is easier to overload the generator. A manual transfer switch powers a preset group of circuits and protects against overload by design, at a higher cost. Neither is automatic. For automatic whole-house power you need a standby generator with an automatic transfer switch.

Do I need a permit and an electrician for a generator inlet?

In Texas, Occupations Code 1305.151 requires a license for electrical work unless an exemption applies, and TDLR says SB 1252 did not remove that requirement. In Florida, work needs a licensed electrician or the owner exemption in 489.503(6), plus the local permit. Check with your city or county; permit rules vary.

What cord do I need from generator to inlet?

Use a heavy-duty, outdoor-rated cord set made for the inlet's amperage and the generator's outlet, with all three prongs and no damage. CPSC says its wattage rating must exceed the connected load. We do not give a wire gauge because it depends on current and length. Use the cord and inlet maker's chart.

Can I power my whole house with a portable generator?

Rarely. A 30 amp inlet has a ceiling of about 7,200 watts at 240 volts by simple math, and the safe sustained number is lower. A 3 ton central air conditioner alone lists 3,000 to 3,500 running watts and 5,000 to 6,000 starting watts. Portable setups work best for a chosen set of essentials.

Can I run my AC on a portable generator through an interlock?

A window air conditioner can work on a large enough unit. Central air is hard, because of high starting watts, and many 30 amp inlets cannot supply it with other loads. You must also manage the load by hand. If central air is a must, a standby generator sized for it is the better route.

What is a bonded vs floating neutral generator?

In a bonded design the generator's neutral is tied to its frame, and in a floating design it is not. When a bonded generator feeds a transfer device that does not switch the neutral, two neutral-to-ground connections can exist and generator GFCIs may trip. The right setup depends on both the generator and the transfer equipment. Follow the manuals and ask your inspector. Do not remove bonding hardware on your own.

How much does a generator inlet install cost?

A national cost guide (Homeyou, updated Sept. 2026) lists a portable generator with transfer switch hookup at $990 to $2,909, averaging $1,693, and a transfer switch install at $829 to $2,652. Another (Inch Calculator, 2023) puts permits at $50 to $200. We found no Texas-only or Florida-only figure. Get written quotes.

Can I use a meter collar adapter with a portable generator?

We found no code, state agency or utility source that approves them for homes. Whether one is allowed depends on your utility and inspector. Call both and get the answer in writing, and do not open the meter yourself.

Which NEC edition applies in Texas now?

The 2026 NEC. TDLR adopted it as the state code effective September 1, 2026 (51 TexReg 5776), and Houston reviews permit applications submitted on or after that date under it. Older pages that cite 2023 for Texas are stale. Florida currently uses the 2020 NEC under the 8th Edition Florida Building Code, with the 9th Edition due at the end of 2026.

Sources

This guide was written by our editorial team from the public sources listed above. It is general information, not legal advice; confirm licensing and terms directly with any provider.

New ebook from The Company ChronicleHow to Research Like a Wall Street AnalystFind original sources, analyze trends, and build your own insights. 36 pages with worksheets.Get the ebook · $29Instant PDF download

Business Spotlight

Want us to publish your business?

Our team writes and publishes articles about your business on The Company Chronicle every month, with a link to your website. Plans from $30 a month, cancel anytime.

Publish with us

The Chronicle directory

What are you into?

The Chronicle, coast to coast

Every corner has a story.

The full Chronicle illustration