What Size Generator or Battery Do You Need to Run Your AC During a Power Outage?
How to size a generator or home battery for a central AC using the numbers on your unit's data plate, what a soft starter does, how transfer switches and interlocks work, which permits Texas and Florida require, and how to avoid the carbon monoxide deaths that follow every big outage.
Size for the compressor's starting surge, not just its running load. On the outdoor unit's data plate, RLA (rated load amps) sets running watts, roughly 240 volts times RLA, and LRA (locked rotor amps) shows the much larger starting surge. One soft-starter maker's example puts a 2-ton AC at about 3,480 running watts with a surge up to 8,500 watts. A soft starter can cut that surge sharply. Connect through a permitted transfer switch or interlock, and run any generator outdoors, more than 20 feet from openings.
Key facts
- CDC: operate a generator outdoors more than 20 feet from windows, doors and vents, and never inside a home or garage, even with doors and windows open.
- CDC says more than 400 Americans die each year from unintentional non-fire carbon monoxide poisoning; CPSC, which counts consumer-product deaths only, cites more than 200.
- CPSC: never power house wiring by plugging a generator into a wall outlet (backfeeding); it can electrocute utility workers and neighbors on the same transformer.
- A soft-starter manufacturer's example: a 2-ton central AC uses about 3,480 running watts but can surge to 8,500 watts at startup; the maker says its device cuts startup current by up to 75%.
- Ready.gov: a refrigerator keeps food cold for about four hours without power, and a full freezer holds temperature for about 48 hours.
- Texas rule 16 TAC §25.497 says a Critical Care or Chronic Condition designation does not guarantee uninterrupted electricity.
- Florida §366.15 makes customers with medically essential service responsible for their own backup equipment or power supply.
- Florida's new permit exemption for single-family work under $7,500 (§553.79, effective July 1, 2026) excludes electrical, mechanical, plumbing, gas and structural work.
- The February 2021 Texas winter storm left more than 10 million people without power at its peak, per NOAA; Texas DSHS confirmed 246 storm-related deaths.
Why is an air conditioner the hardest thing to run on backup power?
Most household loads draw about the same power from the moment you switch them on. An air conditioner does not. Its compressor is a large electric motor that has to start against refrigerant pressure. For a fraction of a second to a few seconds at startup, it pulls a surge of current several times larger than what it uses once it is running.
A generator or battery inverter has to supply that surge without its voltage collapsing. If it cannot, one of three things happens: the generator stalls or trips its breaker, the inverter shuts down to protect itself, or the compressor hums and fails to start, which overheats it. That is why people who bought a generator that looks big enough on paper find that it runs the refrigerator, lights and fans but kills itself every time the AC tries to start.
So there are two numbers to plan around:
- Running watts: what the AC uses once it is up to speed. This sets fuel use and battery runtime.
- Starting (surge) watts: the brief peak at startup. This sets the minimum size of the generator or inverter.
One soft-starter maker gives a useful example: a 2-ton central AC may need only about 3,480 running watts, but its startup surge can spike up to 8,500 watts for a few seconds. Your unit will differ, which is why the data plate matters.
How do you read LRA and RLA on your AC's data plate?
Every outdoor condenser has a metal or foil data plate, usually on a side panel. It lists electrical figures for the compressor and the outdoor fan motor. These are the terms you need:
| Label | Stands for | What it tells you |
|---|---|---|
| RLA | Rated load amps (some plates say RLA or "Comp RLA") | The compressor's running current at rated conditions. Use it for running watts. |
| LRA | Locked rotor amps | The current a compressor draws if its rotor is not yet turning: the worst-case starting surge. |
| FLA | Full load amps (often listed for the fan motor) | The outdoor fan's running current. Add it to the compressor. |
| MCA | Minimum circuit ampacity | For sizing wire. Not the same as what the unit actually draws. |
| MOCP / Max fuse or breaker | Maximum overcurrent protection | The largest breaker allowed. Not a measure of actual load. |
| Volts / phase | Usually 208/230 V, single phase in homes | Tells you the generator must supply 240 V, not just 120 V. |
A common mistake is to size a generator from the breaker size or MCA. Those are wiring and safety limits, not loads. Another is to ignore the indoor unit. The indoor blower in the air handler or furnace also runs whenever the AC cools, and in a heat pump system with electric heat strips the strips can draw far more than the compressor. Find the indoor unit's plate too.
Variable-speed (inverter) compressors are different. These systems ramp the compressor up slowly through electronic drive controls, so their starting surge is much lower than an older single-speed unit's. Check the manufacturer's installation manual for its generator guidance.
What size generator do you need to run central AC? The step-by-step math
You can estimate the size yourself from the data plates. The numbers below are a worked example, not your unit's figures. Electrical loads are approximate because real power also depends on power factor and voltage, so treat the result as a planning estimate and confirm with a licensed electrician.
- Running watts of the outdoor unit. Multiply volts by the compressor RLA plus the fan FLA. Example: 240 V x (14 A + 1 A) = 3,600 watts.
- Running watts of the indoor blower. Use the indoor unit's plate. Example: a blower drawing 4 A at 240 V = 960 watts. Many newer variable-speed blowers use less.
- Other loads you will run at the same time. Refrigerator, lights, fans, phone chargers, a medical device, the furnace controls. Add their running watts from their labels.
- Starting surge. The worst case is volts x LRA. Example: 240 V x 76 LRA = about 18,000 watts for a moment. Real surges are often lower and last only a fraction of a second, but this is the number a generator with weak surge capacity will fail on.
- Add it up. The generator's running rating must exceed all running loads together. Its surge rating must exceed the AC's starting surge plus everything else already running when the compressor kicks on.
A worked example
| Load | Running watts |
|---|---|
| Outdoor unit (compressor + fan) | 3,600 |
| Indoor blower | 960 |
| Refrigerator | (from its label) |
| Lights, fans, chargers | (from labels) |
| Starting surge, AC compressor (240 V x 76 LRA) | about 18,000 for a moment |
In this example, the running load of the AC alone is about 4,560 watts, which many mid-size portable generators can carry. The starting surge is the problem. Without a soft starter, a generator would need very large surge capacity. That is why the same soft-starter maker says a 4-ton AC usually needs a 17,000-watt generator without help, but could run on a 7,100-watt generator with a soft starter, assuming no other large loads start at the same moment.
Tip: always plan for the AC to start last. Turn on the refrigerator and lights first, let the generator settle, then let the thermostat call for cooling. Never let two motors (AC and well pump, say) try to start at once.
What is a soft start kit for an AC?
A soft starter is a small electronic module installed in the outdoor unit's electrical compartment. Instead of letting the compressor slam on at full voltage, it controls the current during startup so the motor comes up to speed more gently. The peak current drops, and so does the size of generator or battery inverter needed to start it.
One manufacturer says its device reduces an AC's startup current by up to 75%, and in its 2-ton example, the startup surge drops from about 8,500 watts to about 3,600 watts. These are the maker's own figures; results vary by compressor, refrigerant pressure and outdoor temperature.
What to know before adding one
- It is a modification to the AC. In Texas, AC repair and modification for the public must be done through a TDLR-licensed air conditioning and refrigeration contractor. In Florida, it is work for a licensed AC or mechanical contractor. See Texas and Florida licensing.
- Check the warranty. Ask the AC manufacturer or installer whether adding a soft starter affects your equipment warranty. Keep the answer in writing. See HVAC warranty registration.
- It may not apply. Variable-speed inverter compressors already start softly and usually do not use add-on soft starters.
- It helps on the grid too. Lower starting current means less light flicker when the AC starts, which some owners notice on long wire runs.
- It does not lower running watts. Fuel use and battery runtime depend on the running load, which a soft starter does not change.
Can a portable generator run your central AC?
Sometimes, if four conditions are met:
- It produces 240 volts. Central AC runs on 240 V. Many smaller portable generators only provide 120 V outlets. Look for a 240 V outlet (often a 30-amp or 50-amp twist-lock) and confirm the generator's 240 V output can be fully used.
- Its surge rating covers your compressor's start. Compare the generator's starting or surge watts to your data-plate math. A soft starter often makes the difference.
- It connects safely. Central AC is hard-wired. You cannot plug it into an extension cord. The generator must feed the house through a transfer switch or a listed interlock on the main panel (see the next section).
- You can keep it fueled and outdoors. A generator big enough for central AC burns significant fuel. You need safe fuel storage and a safe spot outdoors more than 20 feet from openings.
Portable, inverter or standby?
| Type | Typical use for AC | Strengths | Limits |
|---|---|---|---|
| Conventional portable | Window unit by cord; central AC through an interlock or transfer switch if large enough | Lower upfront cost, can be moved | Must be set up in the storm aftermath; fuel handling; noise; CO risk if misused |
| Inverter portable | Window units, mini-splits, smaller central systems with a soft starter | Quieter, cleaner power for electronics, efficient at light loads | Smaller sizes often lack the surge for central AC |
| Standby (permanently installed) | Whole house or selected circuits, including central AC | Starts automatically, runs on natural gas or propane, no refueling with natural gas | Highest cost; needs permits, a pad, gas piping and an automatic transfer switch |
| Battery system | Selected circuits; AC for limited hours | Silent, no fumes, can recharge from solar | Runtime limited by stored kWh; inverter must handle the motor start |
For many households, the practical outage plan is not the central AC at all. A window unit or portable AC in one bedroom, plugged into a portable generator with a heavy-duty outdoor cord, keeps vulnerable people safe on a fraction of the fuel. See our window and portable AC guide.
What is an interlock or a transfer switch, and why can't you just plug in?
When the grid goes down, a generator connected to your house wiring must be isolated from the utility lines. If it is not, its power can flow backward out of your panel, through the transformer on your street, and onto lines that crews think are dead.
CPSC is blunt about the shortcut some people take: never try to power the house wiring by plugging the generator into a wall outlet, a practice called backfeeding. CPSC says it is extremely dangerous and creates an electrocution risk to utility workers and to neighbors served by the same transformer, and that it bypasses some of the home's built-in circuit protection. The double-male "suicide cord" used for this is not a safe tool under any circumstances.
There are three safe ways to connect:
| Method | How it works | Good for |
|---|---|---|
| Extension cords to appliances | Heavy-duty outdoor-rated cords run from the generator to individual appliances. CPSC says each cord's wattage rating must exceed the total load on it, and cords should be long enough to keep the generator far from the house. | Refrigerator, window AC, fans, chargers. Not central AC. |
| Manual transfer switch | A separate subpanel or switch, wired by an electrician, that moves selected circuits from utility to generator. It is physically impossible to connect both at once. | Selected circuits, including the AC circuit if the generator is big enough |
| Interlock kit on the main panel | A listed mechanical plate that prevents the main breaker and a generator inlet breaker from being on at the same time. Power comes in through an inlet box outside. | Lower-cost whole-panel access; you manually manage loads |
| Automatic transfer switch | Senses the outage, starts a standby generator, and transfers load. Often paired with load-management modules. | Standby generators |
Transfer switches, interlocks and generator inlets are electrical work and need a permit and a licensed electrician in both states. They also need to be sized and labeled correctly. Ask the electrician to show you exactly how to switch over and back, and write the steps on a card taped inside the panel door.
Do you need a permit for a standby generator in Florida or Texas?
Plan on it. A standby generator involves electrical work (the transfer switch and wiring), often gas piping (natural gas or propane), and a mounted unit outdoors. Each of those triggers permits in most cities.
Florida
- Florida's new permit exemption for small jobs on single-family homes, under $7,500 and effective July 1, 2026, does not cover electrical, mechanical, plumbing, gas or structural work (§553.79). A generator install does not qualify.
- Starting work that requires a permit without one in effect is a prohibited act under Florida's contracting law (§489.127(1)(h)).
- Gas piping: in Florida, mechanical contractors may run LP-gas and natural gas fuel lines inside buildings, work that air-conditioning contractors cannot do (§489.105(3)(i)). Gas work outside that scope generally falls to licensed gas or plumbing trades. Ask the installer who will hold each permit.
- Outdoor equipment in Florida must resist the wind loads set by the Florida Building Code. The mechanical code rule for exposed equipment (FBC-M 301.15) and flood elevation rules (FBC-M 301.16) show how seriously the state takes anchoring; your building department will tell you what applies to the generator pad.
- Florida requires quick decisions on some single-trade permits for existing homes, which can shorten waits. Ask your county or city building department.
Texas
- Texas has no statewide residential permit system; cities issue electrical, plumbing (gas) and mechanical permits. Houston, Dallas, San Antonio and Austin all run permit offices. Unincorporated county areas may have fewer requirements, so ask the county.
- If the job also touches the AC (for example, adding a soft starter or a new disconnect), that part must be done through a TDLR-licensed ACR contractor, and cities may require a mechanical permit for it.
- Your electric utility may have its own rules for connecting backup generators. Ask before installation.
For more on how AC permits work in each city, see AC permits in Texas and Florida.
Can a home battery like a Powerwall run your AC, and for how long?
A home battery can run an AC if two specs fit your system. Check the battery's spec sheet (any brand) for:
- Usable energy, in kWh. This sets how long it lasts.
- Continuous power and motor-starting (surge) rating, in kW or LRA. This decides whether it can start the compressor at all. Some battery makers publish a locked-rotor-amps figure for motor starting. If your compressor's LRA is higher, you will need a soft starter or a second battery unit.
Battery runtime math
Runtime (hours) = usable battery kWh / average power draw in kW.
The key word is average. A single-speed AC cycles on and off. On a hot afternoon it may run most of the hour; at night, less. So:
Average draw = running kW x the fraction of time the compressor runs (the duty cycle), plus everything else on the battery.
Worked example
- AC running load: 3.48 kW (the 2-ton example above)
- Duty cycle: 50% on a warm evening, so the AC averages 1.74 kW
- Refrigerator, lights, internet and fans: assume 0.4 kW average
- Total average: 2.14 kW
- With 10 kWh usable: 10 / 2.14 = about 4.7 hours
- With 20 kWh usable: about 9.3 hours
At a 90% duty cycle on a hot afternoon, the same 10 kWh would last closer to 2.7 hours (10 / (3.13 + 0.4)). Change the numbers to match your own data plate and battery. Solar panels can recharge a battery during the day, but output drops under the heavy cloud that often follows a tropical storm.
Ways to stretch battery time
- Raise the thermostat several degrees. Fewer compressor minutes is the biggest saving.
- Cool one zone or one bedroom instead of the whole house.
- Shut off electric heat strips, the water heater, the dryer and the oven at the panel during outages.
- Pre-cool before a forecast outage, with blinds closed, so the house starts cold.
How do you manage loads so the AC can run?
Load management means deciding what runs when, so the generator or battery is never asked to do too much at once. It can be manual (you flip breakers) or automatic (a load-management module or smart panel sheds loads for you).
Manual load plan for a portable generator
- Before the outage season, label every breaker clearly. Make a short list of the circuits you will run.
- When on generator power, turn off big loads you do not need: electric water heater, dryer, range, pool pump, electric heat strips.
- Start the generator with no load, then add the refrigerator and lights.
- Turn on the AC circuit last and let the thermostat call for cooling.
- Do not start other motors (well pump, garage freezer) while the AC is starting.
Automatic options
- Load-shed modules on standby generator transfer switches can lock out the AC until enough capacity is free, or drop it when another large load starts.
- Smart panels and smart breakers can prioritize circuits from a phone app, useful with batteries.
- Smart thermostats can be set to a higher setpoint during outages; see smart thermostats.
Keep food and medicine in the plan
Ready.gov says a refrigerator keeps food cold for about four hours without power and a full freezer holds temperature for about 48 hours, and that food at 40°F or higher should be thrown out. Schedule generator time to cover the refrigerator before those limits. Ready.gov also advises having an outage plan for refrigerated medicines and powered medical devices, worked out with your medical provider.
Is it dangerous to run a generator in the garage?
Yes. It is one of the most common ways people die after hurricanes and winter storms. CDC says: never use a generator inside your home or garage, even if doors and windows are open, and operate it outdoors more than 20 feet from windows, doors and vents. CPSC adds basements, crawlspaces and sheds to the list, and warns that deadly levels of carbon monoxide can build up quickly in those spaces and linger for hours after the generator shuts off, even with fans running.
Carbon monoxide (CO) is colorless and odorless. CPSC notes you may be exposed even if you do not smell exhaust. CDC estimates more than 400 Americans die each year from unintentional, non-fire CO poisoning, and more than 100,000 visit an emergency room. CPSC, which counts only consumer-product deaths, cites more than 200 a year. People who are asleep can die before they notice symptoms.
Generator safety rules
- Place the generator outdoors, more than 20 feet from windows, doors, vents and attached garages, with the exhaust pointed away from the house.
- Do not run it in a carport, under a closed-in porch, or next to a window AC that could pull fumes inside.
- Install battery-operated or battery-backup CO alarms on every level of the home and outside sleeping areas. CPSC says alarms should meet a current safety standard such as UL 2034 and that batteries should be tested monthly.
- If anyone feels sick, dizzy or weak, get to fresh air right away and call 911. CPSC lists headache, dizziness, weakness, nausea, vomiting, sleepiness and confusion as CO symptoms.
- Keep the generator dry. CPSC advises running it under an open, canopy-like structure on a dry surface where water cannot reach or pool, and drying your hands before touching it.
- Turn it off and let it cool before refueling; gasoline spilled on hot parts can ignite. Store fuel outside living areas in labeled safety containers, away from fuel-burning appliances.
For more on CO alarms and gas appliances, see carbon monoxide and gas furnace safety.
Why didn't your AC restart after the power came back?
Outages and the surges that come with power restoration cause a predictable set of AC failures. Work through these before you call, and call if any of them repeat.
| What you see | Likely cause | What to do |
|---|---|---|
| Thermostat blank | Thermostat lost power or needs new batteries; tripped breaker or blown fuse for the air handler; smart thermostat needs to reconnect | Replace batteries; check the indoor unit breaker; reboot the thermostat |
| Thermostat on, nothing runs for a few minutes | Built-in compressor delay after power returns | Wait a few minutes before assuming a fault |
| Indoor fan runs, outdoor unit silent | Tripped outdoor breaker, pulled disconnect, or a failed capacitor or contactor | Check the breaker once; if it trips again, stop and call a technician |
| Outdoor unit hums but fan does not spin | Failed run or start capacitor, common after surges | Turn it off now to protect the compressor; call for repair |
| System runs but blows warm air | Compressor not starting, refrigerant issue, or damaged outdoor unit | See AC blowing warm air |
| Water in the drain pan, system off | Condensate float switch tripped | See AC leaking water |
Prevention helps. Turning the AC off at the thermostat and breaker during an outage, and restoring it only after power has been stable, protects it from the on-off cycling and surges that come when the grid is being restored. An HVAC-rated surge protector adds another layer. For the full troubleshooting order, see the AC not working checklist.
Is a whole-house generator worth it in Texas? What Beryl and Uri taught
Whether a standby generator is worth it depends on how often you lose power, for how long, and who in the house cannot go without cooling or powered medical equipment. Two recent Texas events show the stakes.
- Winter Storm Uri, February 2021: NOAA's State Climate Summary for Texas says the storm and extreme cold caused a spike in power demand that led to widespread multi-day blackouts. At the peak, more than 10 million people were without power, and Texas DSHS later confirmed 246 storm-related deaths across the state. Uri showed that the main grid itself can fail, not just neighborhood lines.
- Hurricane Beryl, July 2024: NOAA notes Beryl made landfall on the Texas coast on July 8, 2024, with widespread wind damage and more than 50 tornadoes in the region. A summer hurricane means outages land in peak heat, when an AC failure becomes a health risk for older adults.
Questions to answer before buying
- Does anyone in the home rely on powered medical equipment or have a condition made dangerous by heat? Texas's Critical Care designation does not guarantee power (16 TAC §25.497), so backup becomes your responsibility.
- How many outage days have you had in the last few years, and how long did each last?
- Do you have natural gas service? Natural gas standby units avoid refueling, though gas service can also be interrupted in severe events.
- Would a smaller plan do? A portable generator with a window unit, or a battery for a few circuits, may cover the real need at lower cost.
- Are there HOA rules on generator placement or noise? See HOA and condo AC rules.
Get at least two written quotes that list the generator size, the transfer switch type, what circuits it will carry (including whether it can start your AC), gas piping, the pad, permits, and the maintenance schedule. Standby generators need regular exercise and service to start when needed.
Low-income Texas households in a life-threatening energy crisis should know that the state's LIHEAP plan for federal fiscal year 2026 lists generators among the crisis items local CEAP agencies may provide. See heat safety without AC for how to apply.
How should Florida households plan for multi-day outages after a hurricane?
Florida outages after major hurricanes can stretch for days in hot, humid weather. NOAA's 2025 State Climate Summary for Florida counts 100 hurricanes affecting the state from 1900 to 2024, including 22 since 2000, and describes back-to-back landfalls from Helene and Milton in 2024. A good plan covers people first, then the house.
- People with medical needs: under Florida §366.15, utilities certify medically essential service on a Florida physician's form and must notify you of scheduled interruptions, but the customer is responsible for backup power and an outage plan. If someone would need help evacuating or in a shelter, register on the county special needs registry (§252.355).
- Cooling for one room: a window unit plus a portable generator or battery is often the most reliable post-storm setup. Test it before the season.
- Generator placement: pick the outdoor spot in advance, more than 20 feet from windows and doors, protected from rain, and where it will not be in floodwater.
- Fuel: stations may be closed or out after a storm. Store fuel safely outside living areas, rotate it, and follow the generator maker's storage guidance.
- Restart the central AC carefully once grid power returns. See hurricane prep and restart steps.
Florida's price gouging law (§501.160) applies to equipment and supplies needed because of a declared emergency, including generators and fuel. Buy before the season; prices and availability get worse once a storm is forecast.
Texas and Florida at a glance: backup power for AC
| Issue | Texas | Florida |
|---|---|---|
| Main outage risks | Summer hurricanes on the Gulf Coast; winter grid events (Uri, 2021) | Hurricanes statewide; multi-day post-storm outages |
| Medical utility designation | Critical Care / Chronic Condition (16 TAC §25.497); no guarantee of power | Medically essential service (§366.15); customer responsible for backup |
| Permits for standby generators | City electrical, gas and mechanical permits; county rules vary | Required; the $7,500 small-job exemption excludes electrical and gas work (§553.79) |
| Who modifies the AC (soft starter) | TDLR-licensed ACR contractor | Licensed AC or mechanical contractor |
| Help for low-income households | CEAP crisis assistance can include generators (FFY 2026 LIHEAP plan) | LIHEAP crisis and home energy benefits through local agencies |
| Price gouging law | DTPA §17.46(b)(27) in declared disasters | §501.160 in declared emergencies |
How to choose a provider
- Photograph the data plates on your outdoor unit and indoor unit and write down RLA, LRA, FLA and voltage.
- Calculate running watts (volts x amps) and the worst-case starting surge (volts x LRA).
- Add every other load you plan to run at the same time.
- Ask a licensed HVAC contractor whether a soft starter fits your compressor and whether it affects the warranty.
- Choose a generator or battery whose surge rating covers the AC start and whose running rating covers all loads.
- Have a licensed electrician install a transfer switch or listed interlock under permit; never backfeed through an outlet.
- Label your breakers and write a one-page switch-over and load plan.
- Pick and prepare an outdoor generator spot more than 20 feet from windows, doors and vents.
- Install CO alarms with battery backup on every level and outside sleeping areas; test monthly.
- Store fuel outside living areas in labeled safety containers.
- File a Texas Critical Care or Chronic Condition form, or a Florida medically essential form, if someone relies on powered medical equipment.
- Test-run the whole setup, including starting the AC, before hurricane season and before winter.
Related ac and heating guides
- How Do You Protect Your AC From a Hurricane, and When Is It Safe to Turn It Back On?
- No AC During a Heat Wave: How Do You Keep Seniors, Kids and Pets Safe Until It Is Fixed?
- Is My Gas Furnace Safe? Carbon Monoxide, Cracked Heat Exchangers and First-Freeze Startup in Texas and Florida
- AC Stopped Working in the Heat? The 15-Minute Checklist Before You Call
- Window and Portable AC Units: How to Size, Power and Use Stopgap Cooling When Your AC Breaks in Texas or Florida
- Do You Need a Permit to Replace an AC in Texas or Florida? Rules by City, Who Pulls It, and What Inspectors Check
- Why Is My Heater Not Working? Heat Pump, Heat Strip and Furnace Troubleshooting for Texas and Florida Winters
- What Should I Set My Thermostat To, and Can My Utility Change It? A Texas and Florida Thermostat Guide
AC and heating by state and city
Questions people ask
What size generator do I need for a 3-ton AC?
It depends on the unit, not just the tonnage. Read the outdoor unit's data plate. Running watts are roughly 240 volts times the compressor RLA plus fan FLA, plus the indoor blower. The generator's surge rating must also handle the starting surge, which can approach 240 volts times LRA. Many 3-ton single-speed units need a large generator without a soft starter, and a mid-size one with it. A licensed electrician can confirm.
Can I run my central AC on a 7,500-watt portable generator?
Possibly, if the generator supplies 240 volts, its surge rating covers your compressor's start, and it is connected through a transfer switch or interlock. One soft-starter maker says a 4-ton AC that would need about 17,000 watts could run on about 7,100 watts with a soft starter. Without one, a 7,500-watt generator often cannot start a central AC. Turn off other large loads first and let the AC start last.
Will a soft starter void my AC warranty?
It might, depending on the manufacturer and how it is installed. Ask the AC manufacturer or your installing contractor before adding one, and get the answer in writing. Have it installed by a licensed contractor: in Texas, AC work for the public goes through a TDLR-licensed ACR contractor, and in Florida through a licensed AC or mechanical contractor. Keep the invoice with your warranty papers.
How long will a 13.5 kWh battery run my AC?
Divide usable kWh by your average draw. If your AC runs at about 3.5 kW and cycles half the time, it averages about 1.75 kW; add the refrigerator and lights and you might average about 2.1 kW. A 13.5 kWh battery would last about 6 hours in that case, and much less on a hot afternoon when the AC runs constantly. The battery must also be able to start your compressor.
Do I need a transfer switch to run my AC on a generator?
Yes, for central AC. It is hard-wired, so the only safe connections are a transfer switch or a listed interlock with an inlet, installed by a licensed electrician under permit. CPSC warns never to power house wiring by plugging a generator into a wall outlet, because backfeeding can electrocute utility workers and neighbors. Window units can run from a generator with heavy-duty outdoor-rated extension cords.
Why does my generator shut off when the AC kicks on?
The compressor's starting surge is larger than the generator can supply, so its voltage drops and its breaker or engine protection trips. Fixes include turning off other loads before the AC starts, adding a soft starter to the AC, or using a generator with a larger surge rating. Repeated failed starts are hard on the compressor, so stop trying and fix the cause.
Is it safe to run a generator on a covered porch or in an open garage?
No. CDC says never use a generator inside a home or garage, even with doors and windows open, and to keep it outdoors more than 20 feet from windows, doors and vents. CPSC adds that carbon monoxide can linger for hours in enclosed spaces. Use an open, canopy-like cover on a dry surface away from the house, and install CO alarms with battery backup inside.
Does my utility have to restore my power first if I have a medical condition?
No. In Texas, 16 TAC §25.497 says Critical Care and Chronic Condition designations do not guarantee uninterrupted electricity. In Florida, §366.15 allows emergency disconnections and makes the customer responsible for backup equipment or power. The designations still bring notice of planned outages and added protection from nonpayment disconnection, so file them and plan your own backup power.
Can I run a heat pump's emergency heat on a generator in a Texas freeze?
Electric heat strips draw much more power than the heat pump compressor, often more than a portable generator can supply. During a winter outage, a more realistic plan is to run the heat pump without the strips if the generator can start it, or heat one room safely. Never use a gas stove, oven or grill to heat the home. Ready.gov specifically warns against using a gas stove or oven for heat.
What maintenance does a standby generator need?
Follow the maker's schedule, which usually includes regular automatic exercise runs, oil and filter changes, battery checks and an annual service. Test the transfer switch and confirm it can start your AC, ideally before hurricane season and before winter. A standby generator that has not been exercised or serviced is a common reason backup power fails when it is needed.
Sources
- CDC: Carbon Monoxide Poisoning Basics
- CPSC: Portable Generator Hazards (safety alert, Pub. 5123)
- CPSC: Carbon Monoxide Information Center
- Ready.gov: Power Outages
- Ready.gov: Hurricanes
- Micro-Air (soft-starter manufacturer): What Size Generator Do I Need to Run My Central AC? (Nov. 13, 2025)
- Trane: 8 Ways to Prepare Your AC for Storms (Sept. 12, 2024)
- 16 Tex. Admin. Code §25.497, Critical Load, Critical Care and Chronic Condition Customers
- Florida Statutes §366.15, Medically essential electric public utility service
- Florida Statutes §252.355, Registry of persons with special needs
- Florida Statutes §553.79, Permits
- Florida Statutes §553.792, Building permit application to local government
- Florida Statutes Chapter 489 (Contracting)
- Florida Statutes §501.160, Rental or sale of essential commodities during a declared state of emergency
- Florida Mechanical Code 2023 (8th ed.), Chapter 3, via UpCodes
- City of Orlando: Residential Building Permit Exemption (HB 803)
- Texas Occupations Code Chapter 1302, Air Conditioning and Refrigeration Contractors
- Texas Business and Commerce Code Chapter 17 (DTPA)
- TDHCA: LIHEAP Model Plan, Federal Fiscal Year 2026 (Amendment 1)
- NOAA State Climate Summaries 2025: Texas
- NOAA State Climate Summaries 2025: Florida
- Houston Permitting Center: Mechanical Inspections
- Texas DSHS: February 2021 Winter Storm-Related Deaths, Texas (Dec. 31, 2021)
This guide was written by our editorial team from the public sources listed above. It is general information, not legal advice; confirm licensing and terms directly with any provider.