What Do Small Businesses Need to Know About Commercial Electrical Work in Texas and Florida?
A plain-English primer for business owners and landlords: commercial licensing, three-phase service, lease and build-out responsibility, permits, utility service requests, OSHA rules, NFPA 70B maintenance and emergency lighting.
Commercial electrical work in Texas and Florida must be done by a licensed electrical contractor with the right license class: in Texas a master or journeyman, not a residential wireman; in Florida an EC or local ER contractor, not the residential specialty. Your lease usually decides who pays for build-out and upgrades, the utility decides what service and phase you can get, OSHA Subpart S governs employee safety, and NFPA 70B sets the maintenance benchmark.
Key facts
- A Texas residential wireman may work only in single-family and multifamily dwellings not exceeding four stories (TDLR).
- Texas journeyman industrial electricians may not do residential or commercial work (TDLR).
- Florida ER contractors may work only in their registered jurisdictions and may not contract for alarm systems (DBPR).
- FPL's standard three-phase voltage for loads up to 75 kVA three-phase demand is 120/240 volt open delta; 120/208 and 277/480 wye are used where FPL decides three-phase is required (FPL Electric Service Standards, Nov. 2026).
- FPL requires advance notice of service changes and says new projects can take a few months to plan.
- OSHA requires working space in front of electrical equipment at least 30 inches wide (29 CFR 1910.303(g)(1)).
- OSHA requires live parts to be de-energized before employees work on or near them unless infeasible or more hazardous (29 CFR 1910.333(a)(1)).
- NFPA 70B (2023) changed from a recommended practice to a standard for electrical equipment maintenance.
- Florida must adopt the current edition of NFPA 101, the Life Safety Code, as part of the Florida Fire Prevention Code (s. 633.202).
- Texas commercial landlords may not interrupt tenant-paid utilities except for bona fide repairs, construction or emergencies (Prop. Code 93.002).
Who this guide is for
This guide is for the owner of a restaurant, salon, clinic, shop, warehouse or small office in Texas or Florida, the landlord of a strip center, and the facilities manager who inherited a building nobody documented. It covers what is different about commercial electrical work: licenses, three-phase power, leases, permits, utility service requests, OSHA rules for your employees, maintenance under NFPA 70B, and emergency lighting.
For a business-type checklist (restaurant hoods, salon circuits, medical offices, signs), see the companion guide, electrical build-out checklists for restaurants, retail and offices. For workplace safety in depth, see electrical safety for businesses.
What is the difference between a residential and a commercial electrician?
The physics are the same, but commercial work involves different equipment, codes, voltages and paperwork: three-phase service, larger panels and switchboards, conduit systems, emergency lighting, fire alarm interfaces, and plans reviewed by the building department. Licensing reflects some of that.
Texas
- Texas does not issue a separate "commercial electrician" license. A master or journeyman electrician may do commercial work, and all non-exempt work must go through a licensed electrical contractor (TDLR).
- A residential wireman may work only in single-family and multifamily dwellings not exceeding four stories. That license does not cover a shop, restaurant or office.
- A journeyman industrial electrician may work only at chemical and petrochemical plants, refineries, natural gas plants, pipelines and oil and gas operations, and may not do residential or commercial work.
- Electrical sign work has its own licenses: electrical sign contractor, master sign electrician and journeyman sign electrician.
Florida
- A certified electrical contractor (EC) may do all electrical work, all alarm systems and specialty categories statewide. A registered contractor (ER) may do all electrical work, but only in its registered jurisdictions, and may not contract for alarm systems.
- The residential electrical specialty (class code 043) is a residential-only license. Check the class on DBPR before hiring for commercial space.
- A registered electrical contractor may bid jobs that include alarm systems but must subcontract the alarm work (other than raceways) to a licensed alarm or certified electrical contractor (s. 489.537(2)(b)).
- A certified electrical contractor may act as prime contractor when the majority of the work is within the scope of its license (s. 489.516(5)).
Florida's owner-builder exemption also reaches commercial buildings, but only narrowly: an owner may do electrical work on a commercial building with aggregate construction costs under $75,000, for the owner's own use (s. 489.503). Most business tenants do not qualify because they are not the owner, and the exemption never covers anyone the owner hires.
What is three-phase power and does my business need it?
Most homes get single-phase power: two hot wires and a neutral, giving 120 volts for outlets and 240 volts for large appliances. Three-phase service adds a third hot conductor, with the three alternating currents offset from one another. Three-phase runs large motors more smoothly and efficiently and delivers more power over the same size conductors, which is why commercial HVAC, walk-in refrigeration compressors, commercial kitchen equipment, elevators and shop machinery often need it.
What voltages are available?
FPL's Electric Service Standards (November 2026) are a good example of how a utility decides. FPL says single-phase 120/240 volt service is standard throughout its area for residences and for commercial and industrial customers where three-phase is not required "in the opinion of FPL" or not available. In some locations FPL can provide:
| Service (FPL, under 600 volts) | Typical use |
|---|---|
| Single phase, 120/240 volt, three wire | Standard for homes and many small shops and offices |
| Three phase, 120/240 volt, four-wire open delta | FPL's standard three-phase voltage for loads with individual motors of 7.5 to 20 hp, or three-phase demand up to 75 kVA, or total demand up to 150 kVA, where single phase is impractical |
| Three phase, 120/208 volt, four wire wye | Common in retail strips and office buildings; used where FPL decides three-phase is required and open delta is not the standard for the load |
| Three phase, 277/480 volt, four wire wye | Larger buildings and heavier equipment loads, under the same FPL test |
FPL also notes that devices to convert single phase to three phase exist for a wide range of motors, so whether you need three-phase for smaller motors should be discussed with the utility in advance. Over 600 volts, service is negotiated, and customers taking primary voltage own or rent the distribution equipment beyond the meter.
What the numbers mean
- In "120/208," 120 volts is measured from any hot conductor to neutral (for outlets and lights) and 208 volts between two hot conductors (for equipment).
- In "277/480," 277 volts is hot to neutral and 480 volts between hots. Equipment must be rated for the voltage you have. A 240-volt rooftop unit or oven may not run properly on 208.
Other Texas and Florida utilities have their own service standards. Before you sign a lease or buy equipment, ask your electrician to confirm the service voltage, phase and amperage at the meter, and check equipment nameplates against it.
Do I need three-phase? A quick test
| If your business has... | Three-phase is... |
|---|---|
| Lights, computers, a few small appliances, a split-system AC | Usually not needed |
| Commercial cooking line, dish machine with booster heater, walk-in cooler and freezer | Often needed; check equipment specs |
| Rooftop HVAC units above residential sizes | Often needed |
| Machine shop tools, compressors, welding, large motors | Usually needed, or use phase converters where suitable |
| Multiple EV chargers or DC fast charging | Usually needed |
If the building has only single-phase and you need three-phase, your electrician must request it from the utility. Expect equipment changes on both sides of the meter.
How do I add capacity for new equipment?
- List the equipment you plan to add, with nameplate voltage, phase, amps or kW, and how many run at once.
- Have a licensed contractor do a load calculation against your existing service and panel capacity. Sometimes an existing service has room; sometimes a new panel or feeder is enough.
- Check the lease (below). Many commercial leases require landlord approval for electrical changes and set who owns the new equipment.
- Contact the utility early if service must change. FPL says customers must notify it in advance when a service change is being considered, so it can confirm the service and metering remain adequate, and must book a disconnect and reconnect appointment that is coordinated with the local inspection. FPL's construction page warns that planning a new project "can take a few months, so please contact us early."
- Budget for utility charges. If FPL's existing service conductors must be replaced to reach new equipment, FPL says the customer may be responsible for the cost. Temporary and construction services carry nonrefundable charges paid before FPL builds.
- Pull permits and schedule inspections before the utility reconnects.
In Texas competitive areas, the wires utility (for example Oncor or CenterPoint) handles service connections, not your retail electric provider. Oncor's own description of residential responsibility is a useful starting point: the customer owns and maintains the meter base and wiring in it; Oncor owns the pole, transformer and service line. Commercial arrangements follow each utility's service rules, so ask your electrician to confirm with the utility for your site.
Who pays for electrical in a commercial lease build-out?
No Texas or Florida statute decides this. The lease decides, so read and negotiate the electrical terms before you sign. Common lease terms:
| Term | What it means for electrical |
|---|---|
| Tenant improvement (TI) allowance | A set dollar amount the landlord contributes toward build-out. Ask whether it covers electrical service upgrades, panels and fixtures, and how it is paid (direct to contractor, reimbursement, rent credit). |
| Landlord's work vs tenant's work | A work letter should list exactly what the landlord delivers: service size and voltage, a panel with stated amps and spaces, lighting, HVAC. "Vanilla shell" and "gray shell" mean different things to different landlords; get it in writing. |
| Delivery condition and code compliance | Who pays if inspectors require existing building systems to be brought up to code when your permit is pulled. |
| Alterations clause | Whether you need landlord approval, which contractors may work in the building, and insurance requirements. |
| Ownership and restoration | Whether panels and wiring you install become the landlord's property, and whether you must remove them at lease end. |
| Utilities and metering | Separately metered by the utility, submetered, or included in rent. Who pays utility charges for a service upgrade. |
| Repairs and maintenance | Who maintains the panel, feeders and service equipment. Triple-net leases often push this to the tenant. |
| Common areas | Who maintains parking lot and exterior lighting, and how costs are shared (common area maintenance, or CAM). |
Get a licensed electrician to look at the space before signing. A restaurant that discovers a 100-amp single-phase service after signing can face a costly upgrade the lease makes the tenant's problem.
Lease protections the law does give commercial tenants
- Texas utility interruption: a commercial landlord may not interrupt utility service the tenant pays directly to the utility, unless the interruption results from bona fide repairs, construction or an emergency (Property Code 93.002(a)). The same section limits removing doors, locks and fixtures and lockouts.
- Florida nonresidential leases: where the lease is silent on the repair procedure but expressly puts the repair duty on the landlord, and the landlord's failure makes the premises wholly untenantable, the tenant may withhold rent after serving a written notice giving the landlord at least 20 days to make the specific repair (s. 83.201). The tenant pays the withheld rent once the repair is done; if it is not done, the tenant may abandon, keep the withheld rent and end the lease. This applies only to that narrow situation, so talk to an attorney first.
- Texas DTPA: small businesses are often "consumers" under the DTPA, which excludes only business consumers with assets of $25 million or more (Bus. and Com. Code 17.45(4)). That can matter if a contractor misrepresented the work.
How much does commercial tenant build-out electrical cost?
We could not find a dated, public cost study for commercial electrical build-outs in Texas or Florida, so we will not print a per-square-foot range. Here is what drives the number, so you can read quotes intelligently:
- Service size and phase. Whether the existing service supports your equipment, or a new service and utility work are needed.
- Equipment density. A dental office or restaurant needs far more circuits per square foot than a boutique.
- Lighting and controls. Fixture count, controls required by the energy code, and emergency and exit lighting.
- Wiring method. Many commercial spaces need conduit or metal-clad cable rather than the plastic-sheathed cable used in homes.
- Design and plan review. Larger or more complex jobs may need drawings prepared for permit review; ask your building department what your job requires.
- Labor. BLS May 2025 median electrician wages ranged from $24.43 an hour (Orlando) to $29.03 (Austin) in the major Texas and Florida metros, so local wages are not the main source of differences between quotes.
- Materials. The BLS producer price index for nonferrous wire and cable rose about 20 percent between October 2025 and October 2026.
- Schedule. After-hours work to avoid disrupting a business costs more.
Get at least three itemized bids against the same drawings or scope. See how to compare electrical quotes and electrician costs.
How much does it cost to upgrade to three-phase?
It varies too widely for an honest average, and we found no dated public study for commercial three-phase conversions in Texas or Florida. The cost depends on:
- Whether three-phase utility lines already run past your building, or must be extended. Utilities charge for line extensions under their tariffs.
- Whether the utility must replace its transformer or service conductors.
- New service equipment, meter base or current-transformer cabinet, and a new panel or switchboard.
- Re-feeding existing single-phase loads.
- Permits and inspections.
For homes, LBNL's August 2026 survey found utility-side costs passed to customers for service rating increases had a median of $3,500 and ranged widely; commercial work can be larger. Ask the utility for a written estimate of its charges early, and ask whether a phase converter would serve your equipment instead.
What permits are required for commercial electrical work?
- Texas: cities issue permits and inspect; TDLR does not perform local inspections. Work inside city limits must follow local ordinances, and work in unincorporated areas must meet standards at least as stringent as the state code (Occ. Code 1305.201). Houston requires a permit whenever a new outlet or circuit is installed, requires all work to be done by a licensed electrical contractor, and has the contractor schedule inspections. Texas cities may charge building permit fees but not separate registration fees to state licensees.
- Florida: counties and cities issue permits, inspect, and may require plan approval before work begins (s. 489.537(3)). Doing permit-required work without a permit violates s. 489.531. For contracts over $5,000, Florida permit offices require a recorded notice of commencement before the first inspection (s. 713.135). Local governments may also require a bond of up to $5,000 per electrical contractor.
- Code edition: Texas uses the 2026 NEC for permits applied for on or after Sept. 1, 2026. Florida uses the 2020 NEC (8th Edition Florida Building Code) until the 9th Edition, based on the 2023 NEC, takes effect: Dec. 31, 2026 per the Florida Building Commission, while Tampa says Jan. 1, 2027, and to vest under the 8th Edition a permit application must be accepted by Dec. 31, 2026. See NEC adoption in Texas and Florida.
Permits for a business also commonly involve fire department review (alarms, emergency lighting) and sign permits. City-specific details: Houston, Dallas, San Antonio, Austin, Miami, Tampa, Orlando, Jacksonville.
Do I need a licensed commercial electrician for a restaurant kitchen?
Yes. A commercial kitchen involves high-amperage, often three-phase equipment, GFCI protection, connections to hood exhaust and fire suppression controls, and walk-in refrigeration. In Texas that means a licensed electrical contractor with a master electrician (a residential wireman license does not cover a restaurant). In Florida it means an EC or ER contractor licensed for your jurisdiction, not a residential specialty license.
Two Texas exemptions sometimes confuse owners: licensed air conditioning and refrigeration contractors may make the electrical connections supplying HVAC and refrigeration equipment, including the required disconnect (Occ. Code 1305.003(a)(11)), and licensed plumbers may connect certain plumbing appliances to existing circuits. Neither covers new circuits, panels or feeders. See the restaurant build-out checklist.
What are OSHA electrical requirements for small businesses?
If you have employees, OSHA's general industry electrical standards, 29 CFR 1910 Subpart S (sections 1910.301 to 1910.399), apply to your workplace. Key requirements a small business owner should know:
| Rule | What it says |
|---|---|
| 1910.303(b)(1) | Electric equipment shall be free from recognized hazards that are likely to cause death or serious physical harm to employees. |
| 1910.303(f)(2) | Each service, feeder and branch circuit must be legibly marked at its disconnecting means or overcurrent device to indicate its purpose, unless the purpose is evident. Unlabeled panel directories are a common citation. |
| 1910.303(g)(1) | Working space in front of electrical equipment: at least 30 inches wide (or the width of the equipment, if greater), with depth set by Table S-1: 3 feet at 0 to 150 volts to ground, and 3, 3.5 or 4 feet at 151 to 600 volts depending on whether nothing, grounded parts or more exposed live parts face the equipment (Conditions A, B and C). Headroom is 6.5 feet for installations built on or after Aug. 13, 2007 (6.25 feet for older ones). The space must let equipment doors open at least 90 degrees, may not be used for storage (1910.303(g)(1)(ii)), and must be lit where the equipment is indoors; in electrical rooms that lighting may not be controlled by automatic means only. Equipment above or below a panel may stick out no more than 6 inches past its front. |
| 1910.333(a)(1) | Live parts must be de-energized before employees work on or near them, unless the employer can show de-energizing creates additional or increased hazards or is infeasible due to equipment design or operational limits. Parts under 50 volts to ground need not be de-energized if there is no increased exposure to burns or arc explosion. |
| 1910.333(b)(2) | While employees are exposed to de-energized fixed equipment or circuits, the circuits must be locked out, tagged, or both. |
Practical meaning: keep the area in front of panels clear (no storage boxes, mop buckets or shelving), label every breaker, do not let untrained staff open panels, and replace damaged cords and plugs. A 2025 IAEI Magazine article noted that, as of January 2024, OSHA's maximum penalty for serious and other-than-serious violations was $16,131 per violation; OSHA adjusts penalties for inflation, so check the current figure. See electrical safety for businesses.
NFPA 70B: the electrical maintenance standard
NFPA 70B, the Standard for Electrical Equipment Maintenance, used to be a recommended practice. With the 2023 edition, it became a standard. As an IAEI Magazine article on the change put it, "Formerly a recommended practice, NFPA 70B is now the active standard."
What that means in practice:
- NFPA 70B centers on an electrical maintenance program. Owners start by categorizing their equipment and noting the criticality of each piece, and the standard sets how often equipment must be maintained based on several factors, including condition and criticality.
- Whether NFPA 70B is legally mandatory for your building depends on whether a code, an authority having jurisdiction, an insurer or a contract adopts it. Many businesses treat it as the benchmark of reasonable maintenance, and the IAEI article warns that not following it can lead to problems including OSHA involvement.
- Typical program elements include an equipment inventory, single-line diagram, inspection and testing schedule, records, and corrective action tracking.
We could not access the standard's full text, so ask your electrical contractor or engineer to cite the specific NFPA 70B (2023) sections and intervals they are applying to your equipment.
How often should commercial panels get infrared scanning?
Infrared (thermographic) scanning uses a thermal camera to find hot connections, overloaded breakers and failing components while equipment is energized and loaded. It is one of the most common elements of a commercial maintenance program because loose or corroded connections show up as heat long before they fail.
How often depends on the equipment's condition and criticality under your maintenance program, your insurer's requirements, and the manufacturer's guidance. Because we could not verify the specific NFPA 70B intervals from the standard's text, we will not print a number. Ask:
- What interval do you recommend for my main switchboard and panels, and which NFPA 70B table supports it?
- Does my property insurer require scans, and how often?
- Will the scan be done at normal operating load? (Lightly loaded equipment hides problems.)
- Will I get a written report with images, temperature rises, priorities and repair recommendations?
The person opening energized panels for a scan is doing hazardous work; it should be a qualified electrician or thermographer with appropriate protective equipment, under OSHA's work practice rules.
What is a commercial electrical maintenance contract?
A maintenance agreement is a standing contract for scheduled inspections, testing and repairs, often with priority emergency response. A useful agreement spells out:
| Item | What to look for |
|---|---|
| Equipment covered | An inventory list: switchboards, panels, transfer switches, generators, emergency lighting, parking lot lighting |
| Tasks and frequency | Visual inspection, infrared scan, torque checks, cleaning, generator exercise, emergency light tests, tied to NFPA 70B or manufacturer guidance |
| Response times | Emergency response hours, after-hours rates |
| Reporting | Written reports after each visit, deficiency lists with priorities |
| Pricing | Flat fee for scheduled work, rates for repairs, whether parts are discounted |
| Licensing and insurance | TDLR electrical contractor or DBPR EC/ER license; certificate of insurance naming you or your landlord |
| Term and cancellation | Length, renewal, and how to cancel |
Texas electrical contractors must carry at least $300,000 per occurrence, $600,000 aggregate and $300,000 products and completed operations liability coverage. Florida sets amounts by ECLB rule and requires workers' compensation or an exemption.
What is emergency and exit lighting testing?
Emergency lights and lighted exit signs must work when normal power fails, so occupants can find their way out. Their requirements come from the Life Safety Code, NFPA 101, and the adopted building and fire codes.
- Florida: the State Fire Marshal must adopt the current edition of NFPA 101 by reference as part of the Florida Fire Prevention Code, updated every three years (s. 633.202). Local fire marshals enforce it.
- Texas: fire code adoption and enforcement are local; your city fire marshal can tell you which codes apply.
NFPA 101 requires periodic functional testing of battery-powered emergency lighting and written records of the tests. We could not access the current NFPA 101 text to confirm the exact test intervals and durations, so ask your fire marshal or a fire protection contractor for the intervals that apply to your occupancy, and keep a dated test log near the equipment. Generators that power emergency lighting have their own testing and maintenance requirements.
Common inspection findings: dead batteries, burned-out exit signs, lights blocked by new walls or shelving after a remodel, and no test records.
Do commercial buildings need annual electrical inspections?
Neither Texas nor Florida has a general state law requiring an annual electrical inspection of every commercial building. Instead, inspections come from several places:
- Permits: any new work or alteration gets inspected.
- Fire inspections: local fire marshals inspect many occupancies, which can include exit and emergency lighting, fire alarm power, and obvious hazards like blocked panels or extension cords used as permanent wiring.
- Insurance: property insurers often require loss-control inspections or infrared scans.
- Leases: many commercial leases require tenants to maintain systems and provide proof.
- Industry standards: NFPA 70B sets maintenance frequencies based on condition and criticality.
- Condo buildings in Florida: residential condo buildings three habitable stories or more must include electrical systems in their structural integrity reserve study at least every 10 years (s. 718.112(2)(g)).
Who is responsible for parking lot lighting?
It depends on who owns the lights and what the lease says:
- Multi-tenant centers: parking lot lights are usually common areas maintained by the landlord, with costs passed through as common area maintenance (CAM). Check your lease.
- Single-tenant net lease: the tenant is often responsible for all site lighting.
- Utility-owned lighting: some sites lease outdoor lights from the utility under a lighting tariff, in which case the utility maintains them. FPL's service standards include a street lighting section revised for its LT-1 LED lighting tariff, and TECO markets outdoor lighting solutions. If the pole has a utility tag, call the utility.
Lighting outages are a safety and liability issue for customers and employees after dark. Report outages in writing and keep a record of repair dates.
Mechanic's liens on commercial jobs
Both states give contractors and suppliers lien rights on commercial property, with different deadlines from residential work:
- Texas: on non-residential projects, an original contractor must file the lien affidavit by the 15th day of the fourth month after the month the work was completed, terminated or abandoned (Property Code 53.052), and subcontractors and suppliers must send notice of unpaid claims by the 15th day of the third month (53.056). These deadlines took effect Jan. 1, 2022.
- Florida: claims of lien must be recorded within 90 days after the lienor's final furnishing (s. 713.08), and suppliers not in privity with the owner serve a notice to owner within 45 days of starting (s. 713.06).
Tenants should know that liens from tenant work can attach to the landlord's interest in some situations, which is why many leases require tenants to bond off or discharge liens quickly. Collect lien releases before final payments.
Backup power for a business: what Texas and Florida outages teach
Grid events in both states show why many businesses plan for backup power. During Winter Storm Uri in February 2021, ERCOT's peak load shed reached 20,000 MW, and generation out of service peaked at 52,277 MW, about 48.6 percent of installed capacity. Hurricane Beryl in July 2024 disrupted service for 2.7 million Texas customers, according to the PUCT, and about 1 million were still out four days after landfall. Florida businesses face similar hurricane outages.
Options, from simplest to most complete:
| Option | What it does | Key electrical point |
|---|---|---|
| Portable generator with cords to specific equipment | Runs a few critical items, like a cooler or point-of-sale system | Never plug a generator into a wall outlet to backfeed the building. CPSC warns backfeeding creates an electrocution risk for utility workers and neighbors, and OSHA says generators should not be connected to a building system except through properly wired isolation connections. |
| Generator inlet with transfer switch | Powers selected circuits safely from a portable or towable generator | Installed by a licensed contractor, with a permit |
| Permanently installed standby generator with automatic transfer switch | Restores selected or whole-building power automatically | Requires load calculation, fuel planning, permits, and often utility and fire department review |
| Battery storage | Rides through short outages, may pair with solar | Interconnection rules apply if connected to the grid |
Carbon monoxide is the biggest generator danger. CPSC says most portable generator incidents it receives involve CO from generators used indoors or in partially enclosed spaces; keep them outdoors, far from doors, windows and vents. Businesses with refrigeration or medical needs should decide in advance which loads are critical. See standby generators and transfer switches.
Storm and flood recovery for commercial electrical systems
After a hurricane or flood, do not re-energize water-exposed equipment until it is evaluated. NEMA's 2026 guide on water-damaged electrical equipment (NEMA CS 70006-2026) says equipment exposed to water can be extremely hazardous if re-energized without proper evaluation, and salt water is particularly damaging because its residue is corrosive and conductive. That matters along the Texas and Florida coasts.
- Replace, do not recondition: molded-case circuit breakers, GFCI and AFCI devices, ground-fault protection of equipment, surge protective devices, and wiring devices such as switches and receptacles.
- Wire and cable: cable listed only for dry locations should be replaced; wet-location wire may be reused only if its ends were not exposed and it is undamaged, after consulting the manufacturer.
- Panelboards may be reconditioned in some cases, after consulting the manufacturer. Evaluations should be done by qualified personnel, and the guide does not override manufacturer instructions.
Utilities generally require repairs to customer-owned service equipment by a licensed electrician, and any required inspection, before restoring power. FPL says homeowners own the weatherhead, riser and meter box and damaged equipment must be repaired by a licensed electrician; commercial customers likewise own the service facilities on their side of the point of delivery, except FPL's meters. Document all damage with photos before repairs for your insurance claim, and keep the electrician's written evaluation. See flood-damaged electrical and hurricane electrical safety.
How to hire a commercial electrical contractor
- Verify the license class. Texas: TDLR electrical contractor with a master electrician (not a residential wireman). Florida: EC, or ER registered in your jurisdiction (not residential specialty 043). Add alarm or sign licenses if the job includes them.
- Get insurance certificates naming you and your landlord as certificate holders or additional insureds if the lease requires it.
- Ask for comparable projects in occupied commercial spaces like yours, and how they coordinate with landlords, inspectors and utilities.
- Get itemized bids on the same scope or drawings, with permit, utility coordination, emergency lighting and fire alarm interfaces called out.
- Agree on schedule and access: after-hours work, power shutdowns and notice to other tenants.
- Use a written contract with change-order rules, payment milestones tied to inspections, lien releases and warranty.
Our hiring checklist covers license lookups in detail.
How to choose a provider
- Have a licensed electrician check service size, voltage and phase before signing a lease.
- Negotiate the work letter, TI allowance and electrical ownership terms in writing.
- Verify the contractor's license class on TDLR or DBPR.
- List all equipment with nameplate voltage, phase and amps for a load calculation.
- Contact the utility early about any service change.
- Confirm permits, plan review and the applicable NEC edition.
- Keep panel fronts clear and label every circuit (OSHA 1910.303).
- Set up a maintenance program and infrared scans based on NFPA 70B and insurer requirements.
- Keep a dated emergency lighting test log and ask your fire marshal for intervals.
- Collect lien releases and insurance certificates throughout the job.
Related electricians guides
- What Electrical Does a Restaurant, Salon, Clinic or Shop Need? A Build-Out Checklist by Business Type
- Workplace Electrical Safety for Small Businesses: OSHA Rules, Panels, Extension Cords and Inspections
- How Do You Hire an Electrician in Texas or Florida? Licenses, Insurance, Contracts and Red Flags
- How Do You Read and Compare Electrical Quotes? Sample Line Items and Red Flags
- Do You Need an Electrical Permit in Texas, and Can a Homeowner Do the Work?
- Florida Electrical Permits: Owner-Builder Rules, Exemptions, Open Permits and Inspections
- Which Electrical Code Applies? NEC Adoption in Texas, Florida and Their Major Cities
- Whole-Home Standby Generators: How Do You Size, Install, Permit and Fuel One in Texas or Florida?
Electricians by state and city
Questions people ask
Can a residential electrician do commercial work in Texas?
A Texas master or journeyman electrician may do commercial work through a licensed electrical contractor. A residential wireman may not; that license covers only single-family and multifamily dwellings of four stories or less. A journeyman industrial license covers only petrochemical, refinery, gas and pipeline work. Check the license type on TDLR's search.
Can a residential electrical contractor do commercial work in Florida?
Not with the residential specialty license (class code 043), which is limited to residential electrical contracting. Commercial work needs a certified electrical contractor (EC), valid statewide, or a registered electrical contractor (ER) for that city or county. ER contractors may not contract for alarm systems and must subcontract alarm work.
What is the difference between 208 and 480 volt three-phase?
Both are common commercial three-phase services. In 120/208 volt service, outlets get 120 volts and equipment gets 208 volts between hot conductors. In 277/480 volt service, equipment gets 480 volts and 277 volts is available from hot to neutral. The utility decides what is available at your site, and equipment must be rated for the voltage you have.
How long does it take to get new commercial electric service?
It depends on the utility and the work. FPL says planning a new project can take a few months and asks customers to contact it early. Service changes need advance notice to the utility, a coordinated disconnect and reconnect appointment, and local inspection before reconnection. Start the utility request as soon as your equipment list is final.
Does OSHA require me to keep space clear in front of electrical panels?
Yes, if you have employees. OSHA's 1910.303(g)(1) requires working space at least 30 inches wide, or the width of the equipment if greater, with depth per Table S-1: 3 feet at 0 to 150 volts to ground, and 3 to 4 feet at 151 to 600 volts depending on what faces the equipment. Storage in front of panels is a common violation.
Is NFPA 70B mandatory?
NFPA 70B became a standard rather than a recommended practice with its 2023 edition. Whether it legally binds your building depends on whether a code, authority having jurisdiction, insurer or contract adopts it. Many businesses use it as the benchmark for reasonable electrical maintenance, and it bases maintenance frequency on equipment condition and criticality.
Who pays for a service upgrade in a leased space?
The lease decides. Look at the tenant improvement allowance, the landlord's work letter, the alterations clause and ownership terms. If the landlord delivers a space with a stated service size, an upgrade beyond it is usually the tenant's cost unless negotiated. Have an electrician check capacity before you sign.
Who is responsible for parking lot lights at a shopping center?
Usually the landlord, as a common area, with costs passed to tenants through common area maintenance charges. Single-tenant net leases often make the tenant responsible. If the poles carry a utility tag, the lights may be leased from the utility under a lighting tariff, and the utility maintains them.
Can our own maintenance staff do electrical work in our building?
Sometimes, within limits. In Texas, a person regularly employed as a maintenance person or maintenance electrician for a business may do electrical work for that business without an electrician license, as long as they do not work for the public and are not installing equipment during new construction (Occ. Code 1305.003(a)(8)). TDLR also issues a maintenance electrician license (8,000 hours under a master or maintenance electrician, plus an exam). Florida has no comparable employee exemption; instead, a business can obtain an electrical license to work only on its own equipment and is then not treated as a contracting business (s. 489.5315). Build-outs still need a licensed contractor. See our OSHA guide for workplace safety rules.
Sources
- Texas Occupations Code Chapter 1305
- TDLR Electricians program page
- TDLR Residential Wireman license
- TDLR Journeyman Industrial Electrician license
- TDLR Electrical Contractor license requirements
- TDLR Electrical Sign Contractor license
- TDLR Electricians Compliance Guide
- TDLR adopts 2026 NEC (rulemaking notice)
- Houston Permitting Center, Electrical Inspections
- DBPR Electrical Contractors' Licensing Board
- Florida Statutes s. 489.503, Exemptions
- Florida Statutes s. 489.516, Qualifications to practice
- Florida Statutes s. 489.531, Prohibitions; penalties
- Florida Statutes s. 489.537, Application of this part
- Florida Statutes s. 713.135, Notice of commencement and permits
- Florida Statutes s. 713.06, Notice to owner
- Florida Statutes s. 713.08, Claim of lien
- Florida Statutes s. 83.201, Nonresidential untenantable premises
- Florida Statutes s. 633.202, Florida Fire Prevention Code
- Florida Statutes s. 718.112 (structural integrity reserve study)
- Texas Property Code Chapter 93, Commercial Tenancies
- Texas Property Code Chapter 53, Mechanic's Liens
- Texas Business and Commerce Code Chapter 17 (DTPA)
- FPL Electric Service Standards (November 2026)
- FPL, Building and Construction
- Oncor meter FAQ
- Tampa Electric, Damaged meter equipment (site navigation incl. outdoor lighting)
- OSHA 29 CFR 1910.303, General requirements
- OSHA 29 CFR 1910.333, Selection and use of work practices
- NFPA 70B, Standard for Electrical Equipment Maintenance (product page)
- IAEI Magazine, NFPA 70B: What the Change Means for Maintenance, Operations and Safety (Jan. 2025)
- BLS OEWS electricians wages, May 2025, via BLS Public Data API
- BLS Producer Price Index, Nonferrous wire and cable (WPU1026)
- LBNL, panel and service upgrade cost survey (August 2026)
- ERCOT, February 2021 extreme cold weather event presentation
- PUCT report on Hurricane Beryl (November 2024)
- CPSC Portable Generator Safety Alert
- OSHA, Downed electrical wires fact sheet
- NEMA CS 70006-2026, Evaluating Water-Damaged Electrical Equipment
- FPL, Ready to safely receive power
- Florida Building Commission, 9th Edition course text
- City of Tampa, FBC 9th Edition announcement
- TDLR: Maintenance Electrician license
- Florida Statutes s. 489.5315, Proprietary electrical or alarm contractors
This guide was written by our editorial team from the public sources listed above. It is general information, not legal advice; confirm licensing and terms directly with any provider.