Under NFPA 58, which Texas and Florida both adopt, a single propane tank of 125 to 500 gallons must sit at least 10 feet from buildings and the property line, and a 501 to 2,000 gallon tank at least 25 feet (a single tank up to 1,200 gallons may be reduced to 10 feet). Tanks can be buried if built for it, with corrosion protection. In Texas the Railroad Commission licenses installers; in Florida, FDACS does.

Key facts

  • NFPA 58 sets propane tank distances by water capacity; OSHA's matching Table H-23 (29 CFR 1910.110) lists 10 ft for 125 to 500 gal tanks and 25 ft for 501 to 2,000 gal tanks.
  • A single tank of 1,200 gal or less may be reduced to not less than 10 ft if it is at least 25 ft from other LP-gas containers over 125 gal (OSHA Table H-23 footnote).
  • Texas adopted NFPA 58 (2017) and NFPA 54 (2018) effective Sept. 1, 2020, with changes in 16 TAC 9.403.
  • Florida rule 5J-20.002, amended effective Nov. 17, 2026, adopts NFPA 58 and NFPA 54 (2024) and NFPA 110 (2025).
  • Texas 16 TAC 9.116: underground steel tanks installed since March 1, 2014 need cathodic protection and may not be filled without it.
  • Texas RRC Category D license: $100 original, $70 renewal; individual workers need RRC certification, which expires May 31 each year.
  • Florida FDACS Category V LP Gas Installer license: $200 a year; dealers and installers need $1 million liability coverage and a master qualifier.
  • Since July 1, 2024, Florida qualifier applicants need one year of LP gas experience or a manufacturer certification.
  • Florida 720.3035(6) counts exterior fixed generators and fuel storage tanks as hurricane protection an HOA may regulate but not deny if specifications are met.
  • Fixr (Aug. 2025): a 500 gal tank costs $700 to $2,500 above ground and $1,500 to $3,000 underground, installed.

The short version: what rules apply to a generator propane tank?

A propane tank that feeds a standby generator is a regulated LP-gas system, not a yard accessory. Three layers of rules apply at the same time:

  1. The national code. NFPA 58, the Liquefied Petroleum Gas Code, sets how far a tank must sit from buildings and property lines, how underground tanks are protected from corrosion, how relief valves vent, and how piping is tested. NFPA 54, the National Fuel Gas Code, covers the gas piping from the tank regulator to the appliance.
  2. The state. Texas and Florida each adopt NFPA 58 by rule and license the people who set tanks and run LP-gas lines. In Texas that is the Railroad Commission of Texas (RRC) under Natural Resources Code chapter 113 and 16 Texas Administrative Code chapter 9. In Florida it is the Department of Agriculture and Consumer Services (FDACS) under chapter 527, Florida Statutes, and rule chapter 5J-20 of the Florida Administrative Code.
  3. Your city or county, and your HOA. Local building or fire officials may require a permit and inspection. Floodplain rules can require anchoring. HOA rules can affect where an above-ground tank sits, within limits set by state law.

The two states do not use the same edition of NFPA 58. The RRC adopted the 2017 edition of NFPA 58 and the 2018 edition of NFPA 54, effective September 1, 2020, with Texas-specific changes listed in 16 TAC 9.403. Florida's rule 5J-20.002 was amended effective November 17, 2026 to adopt the 2024 editions of NFPA 58 and NFPA 54 and the 2025 edition of NFPA 110. Most core distances have stayed stable across editions, but details can differ, so an installer working in both states has to check the edition that applies at the job site.

This page explains each rule in plain English. For how big the tank should be and how long it will run your generator, see propane tank size and runtime. For where the generator itself may go, see generator placement and NFPA 37 clearances.

How far does a propane tank have to be from my house and property line?

The distance depends on the tank's water capacity (the size stamped on the nameplate, such as 250, 500 or 1,000 gallons) and whether it sits above ground or underground. NFPA 58 puts the separation table in Table 6.4.1.1. The full NFPA text is copyrighted and not posted free online, so we checked the distances against the federal workplace version of the same rule, OSHA's LP-gas standard at 29 CFR 1910.110, Table H-23, which uses the same structure. Use these numbers to plan, then confirm with your licensed installer against the edition your state adopted.

Water capacity per tankUnderground or moundedAbove groundBetween above-ground tanks
Less than 125 gal10 ftNoneNone
125 to 250 gal10 ft10 ftNone
251 to 500 gal10 ft10 ft3 ft
501 to 2,000 gal25 ft25 ft3 ft
2,001 to 30,000 gal50 ft50 ft5 ft

Source: OSHA 29 CFR 1910.110(b)(6)(ii), Table H-23, distances to the nearest important building or group of buildings. The NFPA 58 table measures to buildings and to the line of adjoining property that can be built on.

Three footnotes that change the answer

  • The 1,200-gallon reduction. OSHA's footnote says the 25-foot distance for 501 to 2,000 gallon tanks may be reduced to not less than 10 feet for a single tank of 1,200 gallons water capacity or less, as long as that tank is at least 25 feet from any other LP-gas container over 125 gallons. That is why many 1,000-gallon residential tanks are set closer than 25 feet.
  • Adding small tanks together. If several tanks at one consumer site add up to 501 gallons or more, the distances for the combined size can apply. Two 500-gallon tanks side by side are treated differently from one.
  • Separate installations. When more than one installation is made on a site, each must be separated from the other by at least 25 feet.

Example

If your installer proposes a 500-gallon above-ground tank on a 60-foot-wide lot in a Tampa or Katy subdivision, the planning number is 10 feet from the house and 10 feet from the side property line. If the plan calls for a 1,000-gallon tank, the base number is 25 feet unless the single-tank reduction applies. On a narrow lot that difference can decide between above ground and buried.

How far must the tank be from windows, the generator, AC units and ignition sources?

Separation from the house is only part of the picture. Tanks have a pressure relief valve that can vent propane if internal pressure climbs, for example on a very hot day or in a fire. The rules keep that vented gas away from places it could get in or ignite.

  • Relief valve discharge and building openings. OSHA 1910.110(b)(10)(i) requires the relief discharge to be at least 5 feet horizontally from any opening into the building that is below the discharge.
  • Air intakes and sealed-combustion appliances. OSHA 1910.110(b)(10)(xiv) requires container relief devices and regulator relief vents to be at least 5 feet in any direction from air openings into sealed combustion appliances or mechanical ventilation air intakes.
  • Never under a building. Relief discharge may not end in or beneath a building, under 1910.110(b)(10)(xiii).
  • Sources of ignition during filling. NFPA 58 has extra distances between the tank's fill connection and sources of ignition, such as an outdoor AC condenser, a pool heater or the generator itself. These numbers are set in the current edition and differ for tanks filled on site. Ask your installer to show you the distance they used.

Tank to generator

The generator is an engine with hot exhaust and electrical parts, so it counts as a potential ignition source. Manufacturer instructions also apply. One major manufacturer's site-selection sheet says the installation must comply with the ICC International Fuel Gas Code, NFPA 37, NFPA 54, NFPA 58 and NFPA 70. Manufacturer A's residential manual says to have the fuel supplier install rigid gas piping and a manual shutoff valve, ending about 12 inches from the generator inlet so a short flexible section can absorb vibration. Your installer has to satisfy both the LP-gas code distance for the tank and the generator maker's clearance from the house. See generator placement rules for the generator side.

Practical spacing checklist

  • Mark windows, doors, dryer vents, crawlspace vents and HVAC fresh-air intakes on a site sketch.
  • Mark the AC condenser, pool equipment and any outdoor kitchen.
  • Mark the property line from your survey, not from the fence. Fences are often off the line.
  • Mark where the delivery truck can park. Hose length limits how far the tank can be from the street.

Can I bury a propane tank for my generator?

Yes. Underground tanks are common in Texas and Florida neighborhoods where an above-ground tank would be visible or where HOA rules push for it. Only tanks built and labeled for underground service may be buried. Above-ground tanks cannot simply be put in a hole.

What underground installation involves

  • Excavation and locate. Call 811 before digging. In Florida that is Sunshine 811; in Texas, Texas 811. Gas, electric, water and cable lines must be marked first.
  • Bedding and cover. The tank sits in a prepared hole with clean backfill. Only the dome covering the valves stays at grade.
  • Corrosion protection. Steel tanks in soil corrode. Underground steel tanks use a coating plus cathodic protection, usually sacrificial anodes (metal blocks, often magnesium, wired to the tank so they corrode instead of the tank).
  • Testing the protection. Cathodic protection must be checked with a meter reading at installation and at intervals afterward.
  • Distances. Burying a tank does not remove the setback. In the separation table, underground tanks up to 500 gallons still need 10 feet from buildings, and 501 to 2,000 gallon tanks need 25 feet unless a reduction applies. The relief valve and fill connection stay at grade under the dome, so the vent distances still matter.

Texas: no fill without cathodic protection

Texas has its own rule on top of NFPA 58. Under 16 TAC 9.116, steel containers and steel piping installed underground, partially underground or mounded on or after March 1, 2014 must include a corrosion protection system. Every licensee servicing the container must monitor the cathodic protection system and document the test results, and those records must be kept. Most important for homeowners: such a container shall not be filled unless a cathodic protection system is installed as the rule requires. The RRC also has rules for system nameplates on underground containers and bars a container built only for underground use from holding liquid fuel while it is above ground or uncovered.

Florida

Florida applies the corrosion protection and underground installation requirements of the NFPA 58 2024 edition adopted in rule 5J-20.002. The tank must be set by a business holding the right FDACS license, covered below.

Underground pros and cons

FactorAbove groundUnderground
LookVisible; may need screeningOnly the dome lid shows
Typical installed cost (Fixr, Aug. 2025, 500 gal)$700 to $2,500$1,500 to $3,000
Corrosion riskPaint and supportsSoil corrosion; anodes needed
Flood behaviorCan float and slide if not anchoredCan float out of saturated soil if not held down
Moving laterAbout $100 to $200 (Fixr)About $1,000 to $1,500 (Fixr)

In coastal Florida and the Houston area, high groundwater matters. An underground tank that is low on fuel is buoyant. Your installer should explain how the tank is held in place, which is the next topic.

Does a propane tank need to be anchored in a flood zone?

In practice, yes, if the site can flood. A propane tank is a sealed steel container. When floodwater rises around it, a partly empty tank floats. Floating tanks tear their piping loose and release propane. After major Gulf storms, loose tanks are a known hazard for responders.

What the rules say

  • Federal floodplain rules. Communities in the National Flood Insurance Program must apply 44 CFR 60.3. It requires new construction and substantial improvements in flood hazard areas to be adequately anchored to prevent flotation, collapse or lateral movement, and to be built with electrical, heating, plumbing and other service facilities designed or located so water cannot enter or build up in the components during flooding. Local floodplain administrators apply these rules to equipment like fuel tanks and generators through local ordinances and the building code.
  • NFPA 58. The LP-gas code contains provisions for containers in areas subject to flooding. We could not load the 2017 or 2024 text to quote the exact wording, so we do not restate it here. Ask your installer to show you the section they followed.
  • Building code and local ordinance. In Florida, the Florida Building Code and county floodplain ordinances apply. In Texas, the city or county floodplain administrator applies its flood damage prevention ordinance. Many require tanks in special flood hazard areas to be anchored or elevated.

How tanks are anchored

  • Above ground: the tank is strapped to a concrete pad or to helical ground anchors (large screws driven into soil), or elevated on a platform above the design flood elevation.
  • Underground: the tank is strapped to a concrete deadman (a buried concrete weight) or to ground anchors so it cannot rise when the soil is saturated.

Ask for the anchoring design in writing. If your adjuster or floodplain official asks how the tank is secured, you want a drawing, not a verbal promise. For generator elevation and wind anchoring, see generators in flood zones and hurricane winds.

Who is allowed to install a propane tank in Texas?

In Texas, LP-gas work is licensed by the Railroad Commission of Texas, Alternative Fuels Safety department, not by TDLR.

  • The law. Natural Resources Code 113.081 requires an RRC license for container activities (including sale and installation of containers) and systems activities, which include laying or connecting pipes and fittings that serve LP-gas systems and appliances.
  • Company license. The RRC says companies, including sole proprietors, need an RRC license to install, service, sell or repair LP-gas equipment. A Category D license (general installers and repairmen) authorizes the sale, service and installation of LP-gas containers and service, installation and repair of piping and appliances. Under 16 TAC 9.6 the original fee is $100 and renewal is $70. A Category E license (retail and wholesale dealer) covers storage, sale, transportation and distribution of LP-gas and most other activities; original fee $750, renewal $300.
  • Individual certification. Each worker doing the job needs RRC certification by exam. The Service and Installation exam, numbered B-3, qualifies an individual for all LP-gas activities on stationary systems, including containers and appliances, but not filling containers or driving a transport. All certifications expire May 31 each year, and most need a first-year training course and continuing education every four years.
  • Plumbers and AC contractors. Under 16 TAC 9.13, Texas master or journeyman plumbers and Class A or B air conditioning and refrigeration contractors can register with the RRC for an exemption from Category D licensing and exams. The fee is $50, and the exemption is not effective until the card is issued. The RRC says only the individual exemption holder may then do LP-gas work; their unlicensed helpers may not.

Electrical work is separate

The tank and gas line are LP-gas work. Wiring the generator and transfer switch is electrical work licensed by TDLR under Occupations Code chapter 1305. A crew may need both an RRC license and a TDLR electrical contractor license, or two subcontractors. See who can install a generator in Texas.

Paperwork the RRC requires

For stationary commercial-use LP-gas facilities under 10,000 gallons aggregate water capacity, licensees file a Completion Report (LPG Form 501) within 30 days of installing a container, with a $10 fee per container. Facilities of 10,000 gallons or more need plan approval on LPG Form 500 ($50) before installation and notice to property owners. The RRC page describes Form 501 for commercial use; whether a single-family home tank requires it is not clear from that page, so ask the installer or call the RRC. Licensees must keep records of pressure tests and leakage tests for at least five years under 16 TAC 9.4.

How to check a Texas license or file a complaint

Ask for the company's RRC LP-gas license number and the installer's certification. The RRC Alternative Fuels Safety department publishes licensing pages and takes complaints through its website (rrc.texas.gov, Alternative Fuels section). If you smell gas, leave the area and call 911 and your propane supplier first.

Who is allowed to install a propane tank in Florida?

In Florida, LP gas is licensed by the Florida Department of Agriculture and Consumer Services (FDACS), Division of Consumer Services. FDACS licenses businesses that sell, store or dispense LP gas and that install, service or repair LP gas containers, systems or appliances, and it investigates LP gas accidents.

LicenseWhat it coversFee (FDACS)
Category I LP Gas DealerSelling LP gas and installing and servicing LP gas appliances and equipment$400 per year
Category V LP Gas Installer (LI)Installing, servicing, designing, modifying and repairing piping, tubing, appliances, equipment and LP gas storage tanks$200 for one year, $400 for two, $600 for three
  • Insurance and qualifier. Category I dealers and Category V installers must carry at least $1 million in bodily injury and property damage liability insurance, pass a state exam and employ a full-time master qualifier at the licensed location.
  • New experience rule. Effective July 1, 2024, applicants for Category I or Category V qualifier certification need at least one year of verifiable LP gas experience or an LP gas manufacturer professional certification.
  • Exams. Under 527.0201, applicants for Category I, II or V licenses must pass a written exam with at least 70 percent in each area tested; the exam fee is $20.
  • Definition. Section 527.01(10) defines a Category V installer as a person whose services include design, installation, servicing, altering or modifying apparatus, piping, tubing, tanks and equipment for liquefied petroleum or natural gas.
  • Penalties. Section 527.02 makes it a third-degree felony to intentionally or willfully engage in licensed LP gas activities without a license, and each business location must be licensed separately. Section 527.06 sets civil penalties of up to $25,000 per violation per day.

Plumbers in Florida

Florida 489.105 includes installing natural gas and liquefied petroleum gas lines within a plumbing contractor's scope. So a licensed plumbing contractor may run gas piping, while setting and servicing the LP tank and system are FDACS-licensed activities. Which license your county building department wants on the gas permit varies, so ask. See who can install a generator in Florida.

Note on rule numbers

Older articles cite Florida LP gas rule chapter 5F-11. Those rules were transferred; the current NFPA adoption rule is 5J-20.002, formerly 5F-11.002. Cite the 5J-20 number when talking to officials.

How to check a Florida license or complain

FDACS posts LP gas license information and a complaint form on its LP Gas page (fdacs.gov, Business Services, LP Gas). The consumer line is 1-800-HELP-FLA (435-7352). Ask for the company's FDACS license number before you sign.

Do I need a permit for a propane tank?

Usually, yes, but the permit often comes from the city or county, not the state, and it may be folded into the generator permit.

  • Texas cities. Houston, Dallas, San Antonio and Austin typically handle generator projects through building, electrical and plumbing or gas permits, and some fire departments review LP-gas tanks. Texas S.B. 1252 (2025) limits city regulation of residential energy backup systems of 50 kW or less, but TDLR says licensed electrical work under chapter 1305 and the NEC still applies. The RRC rules on LP-gas still apply statewide. Check with your city before assuming no permit is needed. Details: Texas generator permits.
  • Florida counties and cities. Miami-Dade, Broward, Hillsborough, Orange and Duval permit offices generally require a gas or plumbing permit for the fuel line and an electrical permit for the generator. Some also require a separate LP tank permit or a fire marshal review. Details: Florida generator permits.
  • Texas HOA tanks. Under Property Code 202.019, an HOA may require LP-gas fuel line connections to follow RRC rules and may require nonintegral fuel tanks to comply with municipal zoning and safety codes.

Fixr's August 2025 propane tank cost guide notes that most areas require a permit and fire department inspection for a new tank installation, but did not list a fee. Ask your installer whether the quote includes the permit and who will pull it. The person who pulls the permit is responsible to the inspector.

What inspections and leak tests are required before propane is turned on?

Before a new system is put in service, the installer has to prove the piping holds pressure and has no leaks. There are usually two checks, plus a local inspection.

1. Pressure test of new piping

New gas piping is pressure tested before it is covered or connected. The installer caps the line, pressurizes it with air or an inert gas, and watches a gauge for a set time. Any drop means a leak. Required test pressures and durations come from NFPA 54 or the fuel gas code the local jurisdiction adopted. Many inspectors want to see the gauge holding at the rough-in inspection, before a trench is backfilled.

2. Leak check when gas is introduced

When propane is first let into the system, the installer performs a leak check at operating pressure. Manufacturer A's residential installation manual says to test all fuel connections with soapy water, close the valves and reseal if a leak is found, and check again with the generator running. Manufacturer A's maintenance section calls for leak testing with soap solution at 6 to 8 ounces per square inch (10 to 14 inches of water column) and warns against soaps containing ammonia or chlorine.

3. Local inspection

The city or county inspector checks the tank location, distances, regulator and piping, and the generator connection. In Florida, the generator's electrical work is inspected separately.

Documentation to keep

  • The pressure test result (date, test pressure, time held).
  • The leak check record at gas-in.
  • The final inspection approval from the city or county.
  • The tank's data plate photo, serial number and the installer's license number.
  • For underground steel tanks, the cathodic protection reading at installation.

In Texas, licensees must keep pressure and leakage test records for at least five years under 16 TAC 9.4. Ask for copies for your own file. They help when you sell the house or file an insurance claim.

Out-of-gas situations

If the tank runs dry during a long outage, the system is not simply refilled and restarted. Ask your supplier what it requires before restoring service after a run-out. A leak check is the usual step, because an appliance valve left open while the system was empty could leak when pressure returns. Keep the tank above the level your supplier recommends so the generator does not run it empty.

Can my HOA block an above-ground propane tank?

Texas

Texas Property Code 202.019 protects permanently installed standby generators that run on natural gas, LP gas, diesel, biodiesel or hydrogen, are rated at least 7 kW, are fully enclosed in a manufacturer sound-attenuating enclosure and connect through a transfer switch. An HOA may not prohibit them. But the HOA keeps some control over the fuel side: it may require LP-gas fuel line connections to follow RRC rules and may require nonintegral fuel tanks to comply with municipal zoning and safety codes. It may also require screening when the generator is visible from the street or neighbors in some yard situations, and its location rules cannot raise generator installation cost by more than 10 percent or fuel and electrical line cost by more than 20 percent. Whether screening rules extend to a separate tank depends on the deed restrictions. See Texas HOA generator rules.

Florida

Florida 720.3035(6) treats "exterior fixed generators" and "fuel storage tanks" as hurricane protection. Every HOA must adopt hurricane protection specifications, which can address color, style and other factors and must follow the building code. The board may not deny an application that conforms to those specifications, though it may require you to follow an existing unified building scheme for exterior appearance. Separately, 720.3075(3)(b) bars HOA documents from precluding fuel sources supplied by Category I, II or III LP gas dealers licensed under chapter 527. So a Florida HOA can shape where and how a tank looks, often pushing toward an underground tank, but it should not be able to ban propane outright. Condos are different: 718.113 does not list generators. See Florida HOA and condo generator rules.

Should I lease or buy the tank, and what does installation cost?

Most homeowners either lease a tank from a propane company or buy one. The choice affects who maintains it and who can fill it.

QuestionLeased tankOwned tank
Up-front costOften little or none; Fixr reports many companies lease at no charge after installation, while some charge $150 to $175 a yearYou pay for the tank and setting
Who can fill itUsually only the company that owns itAny licensed supplier you choose
Maintenance and inspectionsThe companyYou arrange them; Fixr lists $50 to $75 for a yearly inspection
Price shopping after a stormLimited to one supplierYou can call several

Installed cost by size (Fixr, updated Aug. 29, 2025)

Tank sizeAbove groundUnderground
250 gal$450 to $1,000Not listed
500 gal$700 to $2,500$1,500 to $3,000
1,000 gal$1,500 to $3,000$2,500 to $5,000

Fixr puts the national average installed range at $1,500 to $3,750, with an average of $2,500. For underground tanks it lists excavation at $75 to $800, trenching about $75, and the tank-to-line connection about $150, with most homeowners paying $600 to $800 for excavation and trenching combined. These are national figures, not Texas or Florida quotes. Generator gas piping from the tank to the unit is usually priced separately. For full project pricing see standby generator cost.

Fuel price differences between states

The U.S. Energy Information Administration reported residential propane at $3.209 per gallon in Texas and $5.167 per gallon in Florida for the week of November 16, 2026, against a U.S. average of $2.817. A full fill of a large tank costs much more in Florida, which is one reason Florida owners should ask about owning versus leasing and about fill policies.

What size tank does a generator need?

Tank size is a runtime and pressure question as well as a code question. Manufacturer B's support article (December 29, 2025) says tanks supplying vapor to its home standby generators must be at least 250 gallons, and larger tanks may be needed depending on installation, fuel demand or climate. That is one manufacturer's specification, so check your model's manual.

Fuel use scales with load. Manufacturer A's installation manual lists its 20 kW residential units at 136 cubic feet per hour of LPG vapor at full load and 82 cubic feet per hour at half load. Using Manufacturer A's conversion of 36.39 cubic feet per gallon, that works out to about 3.7 gallons per hour at full load and 2.3 at half load (our calculation from Manufacturer A's figures). A larger tank means fewer deliveries during a multi-day outage. The Railroad Commission of Texas also notes that a larger consumer tank lets a customer ride through supply shortages.

Bigger tanks also mean bigger setbacks: going from 500 to 1,000 gallons can move you from the 10-foot row of the distance table to the 25-foot row unless the single-tank reduction applies. Full runtime tables: propane tank size and runtime.

Hurricane and freeze readiness for propane systems in Texas and Florida

Before hurricane season (Florida and the Texas coast)

  • Fill the tank before the storm cone forms. Delivery trucks stop running in high winds and roads close afterward.
  • Confirm the anchoring hardware is intact and not rusted through, especially within a few miles of salt water.
  • Know where the tank service valve is and how to close it. Close it only if instructed or if you smell gas and can do so safely.
  • Clear debris and keep the dome lid of an underground tank visible so responders can find it.

After flooding

  • If the tank moved, the piping may be damaged. Stay away, do not operate anything electrical nearby, and call your supplier and 911.
  • Have a licensed technician inspect the regulator. Flooded regulators can fail because water enters the vent.
  • Do not run the generator until fuel and electrical systems are checked.

Winter storms (Texas)

During Winter Storm Uri in February 2021, more than 4.5 million people in Texas lost power, some for as long as four days in below-freezing temperatures, according to the FERC-NERC staff report. Propane demand spikes in cold weather. The RRC notes that cold weather early in the heating season can push propane prices up. Keep the tank fuller in winter, and remember that vaporization slows in very cold weather, which is one reason manufacturers call for larger tanks in cold climates.

How to choose a provider

  • Get your property survey and mark property lines, windows, vents, AC units and air intakes on a site sketch.
  • Call 811 (Texas 811 or Sunshine 811) before any digging for an underground tank or gas line.
  • Choose tank size with the generator's manual minimum and your outage runtime goal in mind.
  • Check the separation distance for that size and decide above ground or underground.
  • In a flood zone, ask the floodplain office what anchoring or elevation it requires and get the design in writing.
  • Verify the installer's license: RRC LP-gas license and certification in Texas, FDACS Category I or V in Florida.
  • Confirm who pulls the city or county permit and whether HOA approval is needed first.
  • For underground steel tanks, get the cathodic protection reading at installation.
  • Witness or get a record of the pressure test and the leak check at gas-in.
  • Keep the final inspection approval, tank serial number and lease or ownership papers in one file.
  • Fill the tank before hurricane season and keep it fuller in winter.

Related standby generator installation guides

Standby generator installation by state and city

Questions people ask

How far does a 500-gallon propane tank have to be from my house?

Under the NFPA 58 separation table, which matches OSHA's Table H-23 in 29 CFR 1910.110, a single tank of 251 to 500 gallons water capacity must be at least 10 feet from the nearest important building, whether above ground or underground. The same 10 feet applies to the line of adjoining property in NFPA 58. Relief valve discharge must also stay at least 5 feet from building openings below it and from mechanical air intakes. Confirm the edition your state uses: Texas uses NFPA 58-2017 and Florida the 2024 edition.

How far does a 1,000-gallon tank need to be from the property line?

Tanks from 501 to 2,000 gallons fall in the 25-foot row of the separation table. OSHA's version of the table includes a footnote allowing the distance to be reduced to not less than 10 feet for a single container of 1,200 gallons or less, if it is at least 25 feet from any other LP-gas container over 125 gallons. Many 1,000-gallon residential installs use that reduction. Your licensed installer must confirm it under the NFPA 58 edition adopted in Texas or Florida.

Can I install my own propane tank?

No in practice. In Texas, Natural Resources Code 113.081 requires an RRC license for installing containers and connecting LP-gas piping, and each worker needs RRC certification. In Florida, installing LP gas tanks and systems requires an FDACS license, and 527.02 makes willful unlicensed LP gas activity a third-degree felony. The supplier will also refuse to fill a system that has not passed a leak check. Hire a licensed company and keep their license number.

Do underground propane tanks need maintenance?

Yes. Steel underground tanks rely on coatings and cathodic protection, usually sacrificial anodes, to stop soil corrosion. The anodes wear out over time, so the protection must be tested with a meter at installation and periodically after. In Texas, 16 TAC 9.116 requires licensees servicing tanks installed since March 1, 2014 to monitor and document cathodic protection, and a tank without it may not be filled. Keep the dome lid clear and ask for the readings.

Will my propane company fill a tank another company installed?

If you own the tank, any properly licensed supplier can usually fill it after checking the system. If the tank is leased, the owner company typically requires that only it fills the tank, because it is responsible for the equipment. Read the lease before signing. Florida owners, where EIA reported residential propane at $5.167 per gallon in November 2026, may value the freedom to shop more than Texas owners.

Does a propane tank need a concrete pad?

Under NFPA 58 as amended in Texas by 16 TAC 9.403, horizontal ASME tanks for permanent above-ground service must be placed on masonry or other noncombustible supports on concrete or masonry foundations, and must not touch the soil. Many installers use precast concrete blocks under each tank foot rather than a full slab. In flood areas, a pad or anchors may also be needed to hold the tank down. Your local inspector will check the supports.

Is a propane tank allowed under a deck or next to a crawlspace vent?

No for the relief valve area. OSHA's LP-gas rule, which tracks NFPA 58, bars relief discharge from ending in or beneath a building and requires 5 feet from building openings below the discharge and from mechanical ventilation intakes. Propane is heavier than air and pools in low spaces, which is why crawlspace vents, window wells and basement openings are a concern. Keep the tank in open air with room for the delivery hose.

How long does it take to get a propane tank installed for a generator?

Setting a tank is often a one-day job once the permit is approved and the site is located by 811. The wait is usually for the permit, the supplier's schedule and the generator itself. Underground tanks add excavation time and an inspection before backfill. Before and right after a hurricane or freeze, supplier schedules stretch. For the whole project timeline, see our installation process guide.

Do I need a separate tank for the generator and my house appliances?

Not necessarily. One tank can feed the house and the generator if it is large enough and the piping and regulators are sized for the combined load. The generator can be the biggest gas user on the property during an outage, so a shared tank empties faster. Manufacturer A says the fuel supply must handle the generator at rated load plus all other gas appliances. Ask the installer to size the regulator and lines for everything connected.

Sources

This guide was written by our editorial team from the public sources listed above. It is general information, not legal advice; confirm licensing and terms directly with any provider.

New ebook from The Company ChronicleHow to Research Like a Wall Street AnalystFind original sources, analyze trends, and build your own insights. 36 pages with worksheets.Get the ebook · $29Instant PDF download

Business Spotlight

Want us to publish your business?

Our team writes and publishes articles about your business on The Company Chronicle every month, with a link to your website. Plans from $30 a month, cancel anytime.

Publish with us

The Chronicle directory

What are you into?

The Chronicle, coast to coast

Every corner has a story.

The full Chronicle illustration