Natural gas gives you fuel that never runs out as long as the gas system keeps flowing. Propane gives you a tank you control and a little more power from the same engine. Here is how the two compare on output, fuel cost, outage history and installation in Texas and Florida.

Pick natural gas if your home already has a gas meter that can carry the generator's full load: runtime is unlimited and fuel costs less per hour. Pick propane if you have no gas main (common in rural Texas and much of Florida) or want fuel stored on your own property. Propane usually yields slightly more kW from the same air-cooled engine, but a 500-gallon tank lasts about a week at half load.

Key facts

  • On one manufacturer's air-cooled 20 kW model, the standby rating is 18 kW on natural gas and 20 kW on LP; its 14 kW model is 12 kW on natural gas and 14 kW on LP (spec sheets G4-272 and G4-270, 2023).
  • The same manufacturer's 38 kW liquid-cooled model carries the same rating on either fuel: 38 kW single-phase, 39 kW three-phase (spec sheet G4-251).
  • At 50% load the 20 kW model burns about 161 cubic feet per hour of natural gas or 82 cubic feet per hour of LP vapor, which is about 2.25 gallons of propane per hour (gallons are our calculation at 36.39 cubic feet per gallon).
  • Fuel pressure at the generator inlet must stay inside the maker's range: 3.5 to 11 inches water column for natural gas on some 20 kW models, and 7 to 11 inches for LP.
  • EIA reported residential propane at $3.209 a gallon in Texas and $5.167 in Florida for the week of Nov. 16, 2026; 2025 average residential natural gas was $19.42 per thousand cubic feet in Texas and $25.48 in Florida.
  • During Winter Storm Uri, U.S. Lower 48 natural gas production fell 28% between Feb. 8 and 17, 2021, and Texas, Oklahoma and Louisiana output fell by more than half at the low point (FERC-NERC report).
  • The Railroad Commission of Texas ordered on Feb. 12, 2021 that gas deliveries to residences, hospitals and other human-needs customers stay first in priority during the emergency.
  • Florida law (527.07) bars anyone except the tank owner, or someone the owner authorizes, from filling an LP-gas container.

The short answer: which fuel fits which home?

Both fuels run the same kind of standby generator. Most home units leave the factory set up to run on either one, and a trained technician can switch them in the field. So the choice is less about the generator and more about your property, your gas service and how you want to handle a long outage.

Your situationUsually the better fitWhy
Suburban Houston, Dallas, San Antonio or Austin home with a gas meter alreadyNatural gasNo tank, no deliveries, unlimited runtime if the meter and pipe can carry the load
Rural Texas or Hill Country home with no gas mainPropaneThere is no other gaseous fuel option; size the tank for your longest expected outage
Florida home with no gas service (true of much of the state)PropaneA buried or above-ground tank gives you stored fuel before a hurricane
Florida home on a gas main in parts of Miami-Dade, Tampa, Orlando or JacksonvilleNatural gas, with a backup planBuried gas lines usually keep flowing in storms, but service can be interrupted if the system is damaged
Home where the gas meter is small or far from the generator spotEither, after a meter and pipe checkA meter upgrade or long pipe run can change the cost math
Household that cannot risk any fuel interruption (life-support equipment)Natural gas plus a propane or battery fallbackTwo independent energy sources beat any single one

The rest of this guide explains each point, with the numbers behind it. If you are still deciding on size, start with our load calculation walkthrough, because the fuel question depends on how big a generator you need.

Does a generator make less power on natural gas than on propane?

Usually yes, for air-cooled home generators. Propane carries more energy per cubic foot of gas: one manufacturer's manuals list a nominal 1,000 Btu per cubic foot for natural gas and 2,500 Btu per cubic foot for LP vapor. The engine can only breathe so much fuel-air mix, so the richer fuel produces a bit more power.

Here are published standby ratings from one manufacturer's residential spec sheets, for 120/240-volt single-phase models:

Model classNatural gas ratingLP ratingDifference
14 kW air-cooled (14RCA)12 kW14 kWAbout 14% less on natural gas
20 kW air-cooled (20RCA)18 kW20 kW10% less on natural gas
38 kW liquid-cooled (38RCLA)38 kW single-phase38 kW single-phaseNone

Two lessons come out of that table. First, the number on the box is often the propane number. If you plan to run on natural gas, size from the natural gas column. A "20 kW" unit that gives you 18 kW on your gas line can be the difference between running two air conditioners or one. Second, larger liquid-cooled units are often rated the same on both fuels, so the gap mostly matters in the 10 to 26 kW range most homes buy.

Converting the fuel changes the rating. The manufacturer's installation manual says to order a new nameplate showing the new fuel and kW after a conversion, and to leave the UL listing information visible.

Heat and altitude matter too

The same spec sheets tell installers to derate output by 2% for every 10 degrees F above 60 F, and by 4% for every 1,000 feet of elevation above 500 feet. On a 95 F Florida or Texas afternoon, that is roughly 7% less output than the nameplate (our calculation from the published guideline). Combine that with the natural gas derate and a "20 kW" generator may deliver closer to 16 or 17 kW on gas in summer. Most of Texas's big metros and all of Florida sit under 1,000 feet, so altitude rarely matters there, but it can in far West Texas.

How much fuel does a standby generator burn on each fuel?

Manufacturers publish fuel use at 25%, 50%, 75% and 100% of rated load. Below are the 60 Hz figures from one manufacturer's spec sheets. Gallons of propane are our calculation, using the maker's conversion of 36.39 cubic feet of LP vapor per gallon.

Load14 kW natural gas (cu ft/hr)14 kW LP (cu ft/hr / gal/hr)20 kW natural gas (cu ft/hr)20 kW LP (cu ft/hr / gal/hr)
25%9345 / 1.212759 / 1.6
50%12460 / 1.616182 / 2.3
75%16375 / 2.1243109 / 3.0
100%19381 / 2.2281136 / 3.7
Weekly exercise6030 / 0.87135 / 1.0

Most homes average somewhere between 25% and 50% load over a full day, because the air conditioner cycles on and off and big loads like the dryer or oven run only part of the time. Use the 50% row as a planning number and the 100% row as a worst case. For a full runtime breakdown, see our runtime and fuel consumption guide.

What does it cost per hour and per day to run on natural gas vs propane?

We multiplied the 20 kW fuel figures above by current federal price data. These are our estimates, not quotes. Your gas bill and your propane supplier's price are the numbers that count.

20 kW generatorTexas natural gasTexas propaneFlorida natural gasFlorida propane
Price used$19.42 per Mcf (2025 avg.)$3.209 per gal (Nov. 16, 2026)$25.48 per Mcf (2025 avg.)$5.167 per gal (Nov. 16, 2026)
Per hour at 50% loadabout $3.13about $7.23about $4.10about $11.64
Per 24 hours at 50% loadabout $75about $174about $98about $279
Per hour at 100% loadabout $5.46about $11.99about $7.16about $19.31

How we did it: natural gas cost equals cubic feet per hour divided by 1,000, times the price per thousand cubic feet (Mcf). Propane cost equals cubic feet per hour divided by 36.39, times the price per gallon. The natural gas prices are EIA's 2025 average residential prices, which spread fixed monthly charges over all gas sold, so your extra cost for each added unit of gas may be somewhat lower. EIA collects residential propane prices weekly only from October through March, so summer prices are less current.

Three takeaways:

  • Natural gas is cheaper per hour in both states, roughly half the cost of propane in Texas and about a third in Florida at these prices.
  • Florida propane is expensive. At $5.167 a gallon, a week-long post-hurricane run at half load costs close to $2,000 in fuel (our estimate), before any delivery fees.
  • Exercise costs are small. If the 20 kW unit exercises 20 minutes a week, it burns about 0.3 gallon of propane or about 24 cubic feet of natural gas each time (our calculation), roughly 17 gallons of propane a year.

Is natural gas reliable in a Texas winter storm? What happened during Uri?

Natural gas is not a magic, unbreakable supply. It is a chain: wells, gathering lines, processing plants, pipelines, local distribution companies and finally your meter. During Winter Storm Uri in February 2021, the start of that chain broke.

  • The FERC-NERC staff report found that wellhead freeze-offs, loss of power to gas facilities and precautionary shut-ins cut supply. U.S. Lower 48 natural gas production fell 28% between Feb. 8 and 17, 2021, the largest monthly drop on record.
  • At the low point on Feb. 17, production in Texas, Oklahoma and Louisiana was down an estimated 21 billion cubic feet per day, more than half of January's average.
  • Natural gas fuel supply problems caused 27.3% of all power plant outages, derates and failures to start during the event, according to the same report. ERCOT shed 20,000 MW of firm load at the worst point.
  • Texas residential gas use hit a record 1.8 billion cubic feet per day that month, 53% above February 2020.

Did homes lose natural gas service?

Here is the key fact for a homeowner: home heating load normally has firm pipeline transportation and the highest priority. The Railroad Commission of Texas issued an emergency order effective Feb. 12, 2021 that kept deliveries to residences, hospitals, schools and other human-needs customers first in line, ahead of power plants. Power plants were cut before homes. The federal report warned, though, that a future cold event could look more like 2011, when several local gas utilities did curtail service to retail customers. We did not find a reliable count of how many Texas homes lost gas pressure during Uri, so we do not give one.

The practical lesson for a Texas gas-generator owner is to make sure your own equipment is not the weak link. Low supply pressure can starve a generator that is already near the bottom of its allowed range. Ask your installer to measure static and running pressure at the generator with every other gas appliance on, and to confirm it stays inside the manufacturer's range. A homeowner with a medical need should keep a second plan, such as a battery system or a portable unit with an approved inlet. See our Texas grid outage guide.

Is natural gas reliable during a Florida hurricane?

In most hurricanes, buried gas mains keep working while overhead power lines come down. One Florida gas utility's storm guidance says natural gas service will likely be uninterrupted throughout a storm, though outages can occur if the system is damaged. It tells customers to leave the meter on so pressure keeps water out of the lines if flooding occurs, and to have any gas appliance that may have been flooded inspected by a qualified plumber or appliance-service contractor before using it.

The weak points in Florida are local: a gas meter set knocked loose by a falling tree, a storm-surge zone where equipment goes underwater, or a utility shutting a damaged section for safety. If you live in a surge or flood zone, ask your utility where the shutoff points are and how restoration works. Then read our flood zone and wind anchoring guide and the Florida hurricane generator guide.

Propane has its own hurricane risk: a tank only holds what was in it when the storm hit, and road closures can delay refills. The answer for most Florida propane homes is simple: fill before the season and again before a named storm.

Is my gas meter big enough for a generator?

This is the question that sinks the most natural gas installs. Your meter and service regulator are sized for the appliances you had when the house was built. A generator is often the biggest gas appliance you will ever add.

One manufacturer's installation manual says to verify that the utility meter's flow rate can supply the generator at rated load plus all other gas-burning appliances, and to contact the gas supplier for a meter upgrade if needed. Here is a simple example of the math (the appliance numbers are illustrative; use the input ratings on your own appliance labels):

ApplianceInput rating (Btu per hour)
20 kW generator at full load (natural gas)281,000
Furnace (example)80,000
Tank water heater (example)40,000
Range and oven (example)65,000
Total the meter may need to carry466,000, or about 466 cubic feet per hour of natural gas

Many older residential meters were set for far less than that. Call your gas utility (in Texas, often CenterPoint Energy, Atmos Energy or Texas Gas Service; in Florida, the utility listed on your gas bill) with the generator's maximum Btu rating and ask whether the meter and regulator can carry the total. Ask about any fee and lead time. Our gas meter upgrade guide covers the process step by step.

What gas pressure does a standby generator need?

Gas pressure for homes is measured in inches of water column (in. w.c.). One manufacturer's spec sheets list these supply pressure ranges:

  • Natural gas: 5 to 11 in. w.c. on several models, and 3.5 to 11 in. w.c. on models built to accept low pressure
  • LP: 7 to 11 in. w.c.

Typical home natural gas service is delivered at low pressure, so the margin can be thin. Pressure must be measured while the generator runs at load, not just when it sits idle.

Do I need a separate gas line, and what size pipe?

Usually yes. Most installers run a dedicated line from the meter outlet (or from the propane tank's regulator) to the generator, with a manual shutoff valve and a short flexible connector at the unit to absorb vibration. One manufacturer's manual says to have the fuel supplier install rigid gas piping and a manual shutoff, then leak-test every connection with soapy water.

Pipe size depends on the generator's Btu demand and the length of the run. One manufacturer's pipe chart for its 20 kW air-cooled model:

Pipe lengthNatural gas (281,000 Btu/hr)LP (340,000 Btu/hr)
25 ft1 in.3/4 in.
50 ft1 in.1 in.
100 ft1-1/4 in.1 in.
150 ft1-1/4 in.1-1/4 in.
200 ft1-1/4 in.1-1/4 in.

Add 8 feet of equivalent length for every 90-degree elbow. A run with six elbows is 48 feet "longer" than it looks. Final sizing follows the fuel gas code your local building department enforces, and the gas piping must be done by a properly licensed person.

Who can install the gas piping?

  • Texas, natural gas: Texas Occupations Code 1301.002 counts gas piping, including piping outside a building that connects it to a gas supply on the premises, as plumbing, so it falls under the Texas State Board of Plumbing Examiners licensing system.
  • Texas, propane: LP-gas systems work requires a Railroad Commission license or an RRC-registered exemption for licensed plumbers and certain air conditioning contractors (16 TAC 9.13). RRC rule 9.134 bars a licensee from connecting a tank to piping installed by an unlicensed person, except piping an individual installed on his or her own single-family home.
  • Florida: Florida 489.105 includes natural gas and LP gas lines in a plumbing contractor's scope, and FDACS licenses Category V LP gas installers who design, install and repair LP and natural gas piping and equipment.

For the full licensing picture, see Texas installer licensing and Florida installer licensing.

Propane: what you gain and what you take on

Propane's big advantage is control. The fuel sits in your yard. Nobody upstream can curtail it. If a hurricane cuts the roads for a week, a full tank still runs the generator.

What you take on:

  • Limited runtime. A 500-gallon tank holds about 400 usable gallons. At 2.25 gallons an hour, that is about 178 hours, or about 7.4 days, for a 20 kW unit at half load (our calculation). Details are in our propane tank size and runtime guide.
  • A minimum tank size. One manufacturer says its home standby generators need a propane tank of at least 250 gallons, partly for runtime and partly to keep fuel pressure adequate.
  • Tank rules and placement. Tanks must follow NFPA 58 distance rules (Texas uses the 2017 edition through RRC rules; Florida adopted the 2024 edition through rule 5J-20.002 effective Nov. 17, 2026). See our propane tank installation rules.
  • Supplier lock-in on leased tanks. In Florida, statute 527.07 says only the tank owner, or someone the owner authorizes, may fill an LP-gas container. If your supplier owns the tank, it controls who fills it.
  • Delivery timing after storms. The RRC notes that a larger consumer tank lets a customer last through supply shortages and that early-season cold can push prices up. Texas rule 16 TAC 9.31 lets the Railroad Commission declare a regional LP-gas supply emergency and ask loading terminals to give priority to trucks bound for affected counties.

Is propane safer than natural gas?

Neither is "safe" or "unsafe" on its own; both are flammable and both are odorized so leaks can be smelled. The difference is where a leak goes. Propane is heavier than air, so it pools low; one manufacturer says to mount propane detectors low in a room. Natural gas is lighter than air and rises, so its detectors go high. Outdoors, a propane leak can collect in low spots, window wells or crawlspace vents, which is one reason tank and regulator placement rules exist. Carbon monoxide from the generator exhaust is the same danger with either fuel; see our carbon monoxide safety guide.

Can I convert my generator from natural gas to propane later?

Most air-cooled home standby units can be converted in the field. One manufacturer's manual describes moving a fuel fitting or turning a fuel selector, then changing the fuel type setting on the controller. It says a trained technician or authorized dealer should do it, and that the generator's rating changes after conversion.

Things to ask before you convert:

  • Does the conversion need a kit, or is it built in?
  • Will the warranty stay in force if a non-dealer does the work? See our warranty guide.
  • Will the regulator, pipe size and supply pressure still be right for the new fuel?
  • Does the controller setting need to change, and will the nameplate be updated?

Can I use both natural gas and propane?

Some installations add an automatic or manual changeover so a propane tank can back up a natural gas supply. This is a custom fuel system, not a standard homeowner add-on, and it must be designed to the fuel gas code with proper valving so the two gases never mix in a utility line. If you want that redundancy, ask a licensed gas installer whether your generator model supports it and what your local inspector requires. Portable dual-fuel and tri-fuel units are a different topic; see our dual-fuel and tri-fuel guide.

What if my neighborhood has no natural gas service?

Then propane (or diesel, for larger and commercial systems) is your choice for a permanently installed standby generator. That is the normal situation in rural Texas and across much of Florida. To check, look for a gas meter on your house, a gas bill, or a gas main marker along your street, and call the gas utility that serves your area to ask whether service is available at your address and what extending it would involve.

If gas service is available but not connected, compare the one-time cost of a new service line and meter against the cost of a propane tank, setting and fills. Our cost guide breaks down both.

Texas HOAs cannot ban a permanently installed standby generator that runs on natural gas or LP gas and meets the other conditions in Property Code 202.019, though they can require LP-gas connections to follow Railroad Commission rules and can regulate screening and placement. See Texas HOA generator rules and Florida HOA and condo rules.

Side-by-side comparison

FactorNatural gasPropane (LP)
RuntimeUnlimited while supply and pressure holdLimited by usable tank gallons
Output on air-cooled unitsAbout 10% to 14% lower on the spec sheets aboveFull rated output
Fuel cost per hour (20 kW, 50% load, our estimate)About $3 (TX) to $4 (FL)About $7 (TX) to $12 (FL)
Upfront fuel infrastructurePipe run, possible meter or regulator upgradeTank (buy or lease), regulators, pipe, fill
Main outage riskUpstream supply problems, local damageRunning dry before a refill arrives
Who regulates in TexasGas utility; plumbing license for piping (TSBPE)Railroad Commission of Texas (16 TAC ch. 9)
Who regulates in FloridaGas utility; plumbing or Category V installer for pipingFDACS (Chapter 527, rule 5J-20)
Leak behaviorRisesSinks and pools low
Best forMetro homes with adequate meter capacityRural homes and most of Florida

How to choose a provider

  • Find out whether your address has natural gas service and who the utility is.
  • Choose a generator size using the natural gas rating if you will run on natural gas.
  • Ask the gas utility whether your meter and regulator can carry the generator plus every other gas appliance.
  • Have the installer measure gas pressure at the generator under load with other appliances running.
  • If propane, size the tank for your longest expected outage and at least the manufacturer's minimum.
  • If you lease a propane tank, read the lease for fill rights, removal terms and fees.
  • Confirm the gas piping installer holds the right Texas (TSBPE or RRC) or Florida (plumbing or FDACS) license.
  • Fill propane tanks before hurricane season and before freeze forecasts.
  • Install CO alarms on every level and gas detectors at the right height for your fuel.
  • Keep a second plan if anyone in the home depends on powered medical equipment.

Related standby generator installation guides

Standby generator installation by state and city

Questions people ask

Is natural gas or propane better for a standby generator?

Neither wins everywhere. Natural gas is cheaper per hour and never needs a delivery, so it is the usual pick for metro Texas and Florida homes that already have adequate gas service. Propane gives slightly more output on air-cooled models and keeps fuel on your property, which matters in rural areas and in much of Florida where there is no gas main. The deciding factors are gas availability, meter capacity and how long you need to run.

How much less power does a generator make on natural gas?

On one manufacturer's air-cooled residential models, the natural gas rating is 10% to 14% lower than the LP rating: 18 kW vs 20 kW on its 20 kW unit and 12 kW vs 14 kW on its 14 kW unit. Its larger liquid-cooled model is rated the same on both fuels. Always size from the column for the fuel you will actually use.

How much does it cost to run a generator on natural gas vs propane per day?

Using a 20 kW unit at half load and EIA prices, we estimate about $75 a day on natural gas and $174 on propane in Texas, and about $98 on natural gas and $279 on propane in Florida. Those are our calculations from manufacturer fuel tables and federal price data, not quotes. Your utility rate and propane contract decide the real number.

Did natural gas fail during Winter Storm Uri?

Natural gas production did. The FERC-NERC report found Lower 48 output fell 28% from Feb. 8 to 17, 2021, and Texas-area production fell by more than half at the low point. But state rules put residential customers first, and the Railroad Commission's emergency order kept homes and hospitals at the top of the delivery priority list. Power plants lost gas supply far more than homes did.

Can I run my generator on natural gas if my gas pressure is low?

Only if the pressure at the generator stays inside the manufacturer's range while it runs at load. Some models accept natural gas as low as 3.5 inches water column; others need at least 5. Ask your installer to measure pressure with the generator and your other gas appliances running. If it drops too low, the fix may be larger pipe, a shorter run or a meter and regulator upgrade from the utility.

Do I need a new gas meter for a generator?

Often, but not always. The meter must carry the generator's full-load demand plus every other gas appliance in the house. A 20 kW generator can need about 281,000 Btu per hour by itself. Give your gas utility the generator's maximum input rating and your appliance list, and ask whether the existing meter and regulator are big enough and what an upgrade costs and how long it takes.

Can I switch my generator from propane to natural gas if gas service arrives later?

Usually. Most air-cooled home standby units are built to run on either fuel and can be converted in the field by a trained technician. The controller fuel setting and nameplate rating must be updated, and the piping and pressure must be checked for the new fuel. Ask the dealer whether the conversion affects your warranty.

Is it safe to keep a propane tank next to my house for a generator?

Yes, when it is installed to code. Tank distances from buildings, openings and ignition sources come from NFPA 58, which Texas applies through Railroad Commission rules and Florida through FDACS rule 5J-20.002. A licensed propane installer sets the tank, regulators and piping. Propane sinks if it leaks, so keep tanks and regulators away from window wells and crawlspace vents.

Who can fill my propane tank if I switch suppliers?

In Florida, statute 527.07 says only the owner of an LP-gas container, or someone the owner authorizes, may fill it. If the old supplier owns the tank, a new supplier generally cannot fill it without that company's authorization. Florida 527.067 also requires a dealer to give at least 5 business days' written or electronic notice before shutting off service, except for hazards. In Texas, check your lease; we did not find an equivalent RRC rule.

Should a Florida homeowner on natural gas still keep backup fuel?

It is worth thinking about. Buried gas lines usually keep working in hurricanes, and one Florida gas utility says service will likely continue through a storm. But damage can interrupt service, and surge zones raise the risk. A household with medical needs may want a second source such as a battery system. Our medical needs guide covers the options.

Sources

This guide was written by our editorial team from the public sources listed above. It is general information, not legal advice; confirm licensing and terms directly with any provider.

New ebook from The Company ChronicleHow to Research Like a Wall Street AnalystFind original sources, analyze trends, and build your own insights. 36 pages with worksheets.Get the ebook · $29Instant PDF download

Business Spotlight

Want us to publish your business?

Our team writes and publishes articles about your business on The Company Chronicle every month, with a link to your website. Plans from $30 a month, cancel anytime.

Publish with us

The Chronicle directory

What are you into?

The Chronicle, coast to coast

Every corner has a story.

The full Chronicle illustration