Local Guide · Hurricane shutters and impact windows
How Should Commercial Buildings Protect Windows and Doors From Hurricanes? Storefronts, Curtain Walls, Warehouses and Essential Facilities
What Florida and Texas codes require for commercial openings, how Risk Category changes the design, how storefronts, curtain walls and rolling doors are tested, and how owners and tenants should handle shutters, insurance and business continuity.
Most coastal commercial buildings in Florida must have impact-resistant glazing or approved impact-resistant coverings on every glazed opening, under Florida Building Code 1609.1.2, and the HVHZ requires the whole envelope to meet impact criteria. The building's Risk Category sets wind speeds and, for hospitals and shelters, tougher tests. Storefronts, curtain walls and rolling doors each have their own test standards, and in Texas catastrophe areas TWIA-insured commercial buildings need TDI windstorm certification.
Key facts
- FBC 1609.1.2 requires glazed openings in wind-borne debris regions to be impact resistant or protected by an approved impact-resistant covering.
- Replacement windows, doors, skylights and garage doors on existing commercial buildings must comply with FBC Chapter 16 (FBC Existing Building 707.4).
- FBC Table 1604.5 places hospitals with emergency treatment, fire and police stations and designated hurricane shelters in Risk Category IV.
- In the HVHZ, the large missile is a 9-pound 2x4 fired at 50 ft/s, or 80 ft/s for Risk Category IV essential facilities (FBC 1626.2.3).
- HVHZ Risk Category II design wind speeds are 175 mph in Miami-Dade and 170 mph in Broward (FBC 1620.2).
- Impact-resistant coverings must be tested at 1.5 times design pressure and permanently labeled (FBC 1609.1.2.4, 1709.9).
- ANSI/DASMA 115 is the referenced impact standard for garage and rolling doors in Florida.
- Since Jan. 26, 2026, window and door installations in Florida threshold buildings require a certified special inspector's threshold inspection, per Miami-Dade.
- TDI says commercial structures insured through TWIA must follow TDI-adopted standards; WPI-1 applications from April 1, 2026 use the 2024 IBC or IRC.
- IBHS (2020) says one in four small businesses will not reopen after a natural disaster.
Do commercial buildings in Florida need impact glass?
In most of coastal Florida, yes, or they need an approved impact-resistant covering over the glass. Florida Building Code (FBC) Building section 1609.1.2 requires glazed openings in wind-borne debris regions to be impact resistant or protected by an impact-resistant covering that meets ANSI/DASMA 115 (for garage and rolling doors), TAS 201, 202 and 203, AAMA 506, ASTM E1996 and ASTM E1886, or another approved impact standard. The code applies to commercial buildings the same way it applies to homes: the question is where the building sits and what Risk Category it falls in.
The FBC defines the wind-borne debris region as the part of the hurricane-prone region within 1 mile of the coastal mean high water line where the ultimate design wind speed (Vult) is 130 mph or more, or anywhere Vult is 140 mph or more. In Miami-Dade and Broward, the High-Velocity Hurricane Zone (HVHZ), FBC section 1626.1 goes further: all parts of the building envelope, including exterior walls, roof, outside doors, skylights, glazing and glass block, must meet the impact test criteria or be protected by an external device that does.
Replacing glass on an existing commercial building
Replacement is where many business owners are surprised. Florida Building Code, Existing Building section 707.4 requires replacement garage doors, exterior doors, skylights and windows to be designed and built to comply with Chapter 16 of the FBC Building. The 25 percent exceptions that let some older homes replace a limited amount of glass without opening protection apply only to one- and two-family dwellings. A storefront owner in Tampa, Miami or on the coast near Jacksonville replacing a damaged storefront should plan for code-compliant impact glass or a compliant covering.
Where the rules are lighter
- FBC 1609.1.2 lets glazing in Risk Category I buildings, such as greenhouses used for growing plants without public access, be unprotected.
- Glazing in Risk Category II, III or IV buildings more than 60 feet above the ground and more than 30 feet above any aggregate-surface (gravel) roof within 1,500 feet may be unprotected. This exception is in the general section; HVHZ buildings follow section 1626.
- Storage sheds not designed for human habitation with 720 square feet or less of floor area are not subject to the mandatory impact standards.
- Inland locations outside the wind-borne debris region, including much of the Orlando area, may not require impact protection by code, though wind pressure ratings still apply. Confirm with the building department and the engineer.
For the full opening-protection rules, see Florida Building Code opening protection and HVHZ requirements in Miami-Dade and Broward.
What is Risk Category, and how does it change the design of a commercial building's openings?
Risk Category is the code's way of saying how much harm would follow if a building failed. Florida Building Code Table 1604.5 assigns every building to one of four categories, and the category changes the design wind speed, the wind-borne debris map used, and in the HVHZ the impact test itself. The FBC table is used in place of ASCE 7 Table 1.5-1.
| Risk Category | Examples from FBC Table 1604.5 |
|---|---|
| I | Low hazard to human life: agricultural facilities, certain temporary facilities, minor storage facilities, screen enclosures |
| II | Everything not in I, III or IV, which covers most offices, retail stores, restaurants, warehouses, hotels and apartment buildings |
| III | Substantial hazard: public assembly with an occupant load over 300; Group E or I-4 (schools, day care) over 250; college buildings over 500; Group I-2 with 50 or more care recipients but no surgery or emergency treatment; Group I-3 (jails); any occupancy over 5,000; power, potable water and wastewater facilities not in IV; certain buildings with toxic or explosive materials |
| IV | Essential facilities: hospitals with surgery or emergency treatment; fire, rescue, ambulance and police stations; designated hurricane and emergency shelters; emergency operations and communications centers; backup power for Risk Category IV buildings; certain buildings with highly toxic materials |
What changes with a higher category
- Higher design wind speeds. In the HVHZ, FBC 1620.2 sets design wind speeds for Miami-Dade at 165 mph (Risk Category I), 175 mph (II), 186 mph (III) and 195 mph (IV), and for Broward at 156, 170, 180 and 185 mph. Higher speeds mean higher design pressures for every window, door and shutter.
- Different debris maps. The FBC uses Figure 1609.3(1) to set the wind-borne debris region for Risk Category II and III buildings (except health care facilities), Figure 1609.3(2) for Risk Category III health care facilities and Figure 1609.3(3) for Risk Category IV. So a hospital or shelter can be inside the debris region where a shop next door is not.
- Tougher missile tests in the HVHZ. FBC 1626.2.3 fires the 9-pound 2x4 large missile at 50 feet per second for most buildings but at 80 feet per second for Risk Category IV essential facilities, and section 1626.3 requires Risk Category IV buildings to keep using the large missile test even above 30 feet, where other buildings may use the small missile test.
Practical tip: the Risk Category should appear on the sealed drawings. If you are a business owner leasing space for a clinic, school, day care or assembly use, ask the landlord's engineer whether your use changes the building's category, because that can change what glass and shutters are acceptable.
What are storefront systems and curtain walls, and how are they tested?
Storefront usually means a framed glass system at street level, with fixed glass, entrance doors and sometimes transoms, typically spanning from floor to a header one story up. Curtain wall is a non-load-bearing glass and metal wall hung from the building structure across multiple floors. Window wall sits between floor slabs, floor by floor. All three are glazed openings under the code.
Testing and labeling
- FBC 1709.5.1 requires exterior windows and sliding doors to be tested and labeled to AAMA/WDMA/CSA 101/I.S.2/A440 or TAS 202, and in the HVHZ to TAS 202 and ASTM E1300 or section 2404 (glass design).
- Assemblies not covered by 1709.5.1 must be tested under FBC 1709.5.2 to ASTM E330 or TAS 202 (TAS 202 in the HVHZ), loaded for 10 seconds at 1.5 times the design pressure, and glass must comply with section 2403. Custom one-of-a-kind exterior doors may instead be designed by a Florida registered design professional with signed and sealed calculations.
- In wind-borne debris regions, storefronts and curtain walls must also pass impact and cyclic pressure testing to ASTM E1886 and E1996 or the HVHZ protocols TAS 201 and 203, or be protected by approved coverings.
- Labels must show the manufacturer, model, positive and negative design pressure, maximum size tested, impact rating, the Florida or Miami-Dade approval number and the test standard; the temporary label stays on until final approval.
- Florida law (section 553.842) requires statewide product approval for windows, doors, panel walls, shutters and impact protective systems, and bars marketing a product as hurricane or wind-borne debris protection unless it is approved.
Field testing after installation
Lab ratings show what a tested sample can do. Field tests show what your installed system does. AAMA 503 covers air leakage and water penetration testing of newly installed storefronts, curtain walls and sloped glazing, as described by a building-enclosure consulting firm, which notes it is often used for pre-occupancy acceptance testing and mid-construction quality checks. Newly installed windows and doors use AAMA 502, which checks air infiltration with ASTM E783 and water penetration with ASTM E1105. Existing storefronts and curtain walls are evaluated with AAMA 501.2 instead. Write the test type, number of tests and retest responsibility into the contract.
Louvers and vents
Mechanical louvers are openings too. FBC 1609.1.2.1 says louvers within 30 feet of grade must meet AMCA 540 or be protected by an impact-resistant cover meeting the large missile test, and louvers that must stay open for life safety, such as providing breathable air, must meet AMCA 540.
Do warehouses need impact-rated overhead and rolling doors?
Large overhead doors are often the biggest openings on a warehouse, distribution center, auto shop or fire station, and a failed door lets wind pressurize the building. The code addresses them directly:
- FBC 1609.1.2 names ANSI/DASMA 115 as the impact standard for garage doors and rolling doors in wind-borne debris regions, and section 1609.1.2.3 requires garage door glazed opening protection to meet an approved impact standard or ANSI/DASMA 115.
- The 2023 FBC references ANSI/DASMA 115 in its 2005, 2012 and 2017 editions for sectional, rolling and flexible garage doors under missile impact and cyclic wind pressure.
- Sectional garage doors and rolling doors also have wind load testing and labeling rules in FBC 1709.5.2.1.
- In the HVHZ, every opening in the envelope must meet impact criteria, with listed exemptions such as vents in garages for four or fewer cars, which rarely help a commercial building.
In Texas, the Texas Department of Insurance (TDI) says garage doors must be tested to ASTM E330, with glass panels rated to ASTM E1996, for windstorm certification in its program. TDI also states that in recent hurricanes garage door failures contributed to 80 percent of home failures; TDI gives no study citation for that figure, and it describes homes, but the physics of a failed large door applies to commercial buildings as well.
Operational questions for businesses
- Is the door rated at the size installed, with the reinforcement or bracing the approval requires?
- Does the door need a manual operator if power is out before or after the storm?
- Are dock seals, vision panels and pass doors also rated?
- Is the wall and header around the door designed for the door's reaction loads? An engineer should check older pre-engineered metal buildings.
See hurricane-rated garage doors and garage door bracing and retrofits for the residential side of the same standards.
Can a business use roll-down shutters or accordions instead of impact glass?
Yes, where the code allows impact-resistant coverings, and in the wind-borne debris region it does: section 1609.1.2 lets glazed openings be "protected with an impact-resistant covering." Many shopping centers, restaurants and offices in Florida and on the Texas coast use roll-down shutters over storefronts because they also give after-hours security. The rules for coverings are specific:
- Testing at 1.5 times design pressure. FBC 1609.1.2.4.1 requires impact-resistant coverings to be tested at 1.5 times the design pressure, positive or negative, determined under FBC 1609 or ASCE 7.
- Labels. FBC 1709.9 requires a permanent label on every shutter showing the approval holder's name and address, the methods of approval, the test standards and the Florida or Miami-Dade approval number. On roll-up shutters the label goes on the bottom of the hood or the bottom slat facing out; on accordions, on the bottom of the locking bar or center mate facing out.
- Installation. Coverings must be installed per the manufacturer's instructions and the product approval, with instructions available to inspectors on site (FBC 1709.9.4).
- No contact with the glass. In the HVHZ, FBC 1626.2.6.1 requires shutters to resist the large missile impacts without deforming enough to contact the glass they protect. Clearance between shutter and glass is part of the design.
The trade-offs
| Factor | Impact storefront or curtain wall | Roll-down or accordion shutters | Removable panels |
|---|---|---|---|
| Storm-day labor | None | Someone must close every shutter | Crew needed to install every panel |
| Works if nobody can reach the building | Yes | Only if closed in advance | Only if installed in advance |
| Daily security | Laminated glass resists entry better than ordinary glass | Strong if closed after hours | Not used daily |
| Storefront visibility when deployed | Business can keep operating | Storefront dark while closed | Storefront dark while installed |
| Power dependence | None | Motorized units need manual override or backup | None |
| Permit in Miami-Dade | Window or door permit | Category 29 permanent shutters; zoning review for permanent storm shutters on commercial buildings | Category 101 removable panels |
Two cautions. First, closed shutters must not leave the building without the exits the fire code requires while people are inside; ask the building official or fire marshal before covering exit doors on an occupied building. Second, a shutter only protects if it is closed in time. A business with many locations should assign who deploys which shutters and test the plan before June. For product types, see roll-down hurricane shutters and accordion hurricane shutters.
Who designs commercial opening protection: the engineer of record and the envelope consultant
On a commercial project, the engineer of record (or architect of record) is the Florida- or Texas-licensed design professional whose sealed drawings establish the building's Risk Category, wind speed, exposure and the design pressures for each opening. Product approvals then have to meet those numbers. For windows on threshold buildings in Florida, Miami-Dade's checklist asks for wind calculations for all openings in the installation under FBC 1620 and ASCE 7-22 Chapter 30.
A building envelope consultant is a specialist, often an engineer or architect, hired by the owner to review the design and installation of the walls, windows, roof and waterproofing as one system. On a storefront or curtain wall job, the consultant typically reviews shop drawings, attends mock-ups, witnesses field tests such as AAMA 503 and inspects flashing and sealant joints. The role is not created by statute; it is a contract role, so define its scope in writing.
Threshold buildings and the 2026 special inspection rule
Florida section 553.71 defines a threshold building as any building greater than three stories or 50 feet in height, or an assembly occupancy over 5,000 square feet with more than 500 occupants. That includes many office towers, hotels, large churches, arenas and convention spaces. Miami-Dade reports that, under a Building Officials Association of Florida binding interpretation of FBC 110.8.1 ratified by the Florida Building Commission on January 26, 2026, all window and door installations in threshold buildings now require a threshold inspection by a state-certified special inspector and a special inspection plan from the engineer of record, along with wood buck calculations when bucks are 1-1/2 inches or thicker, a Threshold Building Affidavit and a special inspector form. Under section 553.79(5), the building's fee owner selects and pays the special inspector, who answers to the building department.
Contractor licensing for commercial openings in Florida
- A general contractor is unlimited in the type of work.
- A building contractor may build commercial buildings up to three stories, or remodel, repair or improve any size building when the work does not affect structural members (section 489.105).
- A specialty structure contractor may install windstorm protective devices (shutters, panels) without height limit, but its window and door assembly scope is limited to Group R (residential) occupancies up to three stories or 30 feet, so it cannot be the prime contractor for impact glass on a commercial storefront (rule 61G4-15.015).
Verify licenses on the Florida DBPR search at myfloridalicense.com. Texas has no statewide contractor license for this work; see Texas window and shutter contractor rules.
Do commercial property owners need permits for shutters and windows?
Yes, in general. Florida requires product-approved shutters and windows, installed under permit and inspected. Local checklists differ, so use your building department's list. Miami-Dade County's published checklists are a useful model:
- Replacement windows, mullions and glass doors: permit application categories 82 and/or 83 (commercial and residential), total square footage, an elevation of each affected wall showing the units replaced, and the current NOA or Florida approval for each product.
- New window or door openings in commercial buildings: category 01 (commercial) along with 82 and/or 83 for glazed openings, with standard details or signed and sealed custom details.
- Shutters and storm panels: category 101 for removable panels or category 29 for permanent shutters, a drawing of opening sizes and locations, the building's mean roof height, and the NOA, with the specific panel and connection marked if the approval covers several.
- Zoning review: Miami-Dade states zoning review and approval are required for the installation, repair or replacement of permanent storm shutters on commercial buildings, including condominiums and apartment buildings.
- Threshold buildings: the added 2026 threshold documents described above.
After a declared disaster, some cities relax specific permits. The City of Tampa's Post-Hurricane Permitting Guide (updated April 2026) says waivers apply only after a declared disaster and only when the Mayor exercises emergency powers, and it lists which items qualify. Do not assume a commercial storefront replacement is exempt; ask the building department in writing. For a city-by-city view, see hurricane window permits in Florida.
How do Texas Gulf Coast rules apply to commercial buildings?
Texas has no statewide building code for private commercial buildings that works the way the Florida Building Code does, but the coast has the TDI windstorm program, which matters for any business that needs wind and hail coverage through the Texas Windstorm Insurance Association (TWIA).
- Who is covered: TDI's designated catastrophe areas are Aransas, Brazoria, Calhoun, Cameron, Chambers, Galveston, Jefferson, Kenedy, Kleberg, Matagorda, Nueces, Refugio, San Patricio and Willacy counties, plus Harris County cities east of State Highway 146 such as La Porte, Morgan's Point, Pasadena and Seabrook.
- Commercial buildings included: TDI says commercial structures must follow its adopted building standards if they will be insured for windstorm and hail through TWIA.
- Current codes: starting April 1, 2026, windstorm Certificate of Compliance applications (WPI-1) must be certified to the 2024 International Residential Code or the 2024 International Building Code; commercial buildings use the IBC. TDI says most catastrophe areas are now inside the windborne debris region under the 2024 codes, so impact-rated glazing or protection is generally required for openings there.
- Notice before work: Texas Insurance Code section 2210.2515(b) requires written notice to TDI before starting construction, repair, alteration or remodeling of a structure for which TWIA coverage is sought.
- Inspections: only TDI appointed qualified inspectors can inspect ongoing construction; any Texas-licensed engineer can inspect completed construction for a WPI-8-E. Under 2210.258(b), TWIA may not insure work begun on or after June 19, 2009 until a certificate is issued, with limited exceptions.
- Products: TDI tells owners to use opening protection tested to ASTM E1886 and ASTM E1996 with a recognized product approval, and warns that a product rated for "Force 12" winds only meets the minimum of a Category 1 hurricane (74 mph).
Houston, Dallas, San Antonio and Austin
Inland and metro buildings outside the catastrophe areas follow their city's adopted codes. Wind still breaks glass there: NOAA's National Centers for Environmental Information reported that a May 2024 derecho, with winds at times above 100 mph, blew out numerous windows in downtown Houston skyscrapers, and Hurricane Beryl in July 2024 caused power outages affecting millions for days. A business in Houston that cannot afford weeks of downtime should treat opening protection as a business continuity decision, not just a code question. See Texas coastal building codes and TWIA coverage and opening protection.
Do commercial insurers give credits for opening protection?
It depends on the policy type and the insurer. Florida section 627.0629 requires rate filings for residential property insurance to include actuarially reasonable discounts or credits for wind mitigation features, including opening protection and window, door and skylight strength. That statute is written for residential property. For commercial property policies, credits for opening protection are a matter of each insurer's underwriting and rating, so ask your agent or broker directly what the carrier recognizes and what proof it needs.
In Texas, TDI says TWIA offers a discount for existing structures that retrofit exterior openings with windborne debris resistant products, and that owners can protect openings a few at a time, with an inspection each time and a final filing confirming all openings are protected. Ask TWIA or your agent how that applies to a commercial policy.
Documents to keep for underwriters
- Product approval numbers (Florida FL numbers or Miami-Dade NOAs) for every window, door and shutter.
- Permit numbers and final inspection records; in Texas, the WPI-8 or WPI-8-E.
- Photos of shutter labels and window labels before the temporary labels are removed.
- The sealed drawings or design pressure schedule.
- A written storm deployment plan for shutters, if you rely on them.
For the residential side, see insurance discounts for impact windows and shutters.
Who pays and who deploys: tenant versus landlord responsibility in a lease
Neither Florida nor Texas has a general statute assigning hurricane protection between commercial landlords and tenants. The lease controls, and many leases are silent or vague about storm shutters and glass. This is general information, not legal advice; a real estate attorney should review your specific lease. These are the points that most often cause disputes:
| Issue | Question the lease should answer |
|---|---|
| Ownership of storefront glass | Is the storefront part of the building shell (landlord) or a tenant improvement (tenant)? |
| Code upgrades | If broken glass must be replaced with impact glass under FBC Existing Building 707.4, who pays the difference? |
| Installing protection | Does the tenant need landlord approval to add shutters, and must they match a unified design? |
| Deployment | Who closes the shutters or installs panels when a watch is issued, and who has the keys or tools? |
| Failure to deploy | Who is responsible for damage if shutters were not closed? |
| Insurance | Which policy covers glass, shutters, inventory and business income, and who carries the deductible? |
| Access after the storm | When can the tenant re-enter, and who boards broken openings? |
| Rent during repairs | Does rent abate while the space is unusable? |
If you are negotiating a lease in Miami, Tampa, Jacksonville, Galveston or Corpus Christi, put the deployment responsibility in writing with names and phone numbers, and attach the shutter layout to the lease. For apartment and rental property issues, see rental property hurricane protection.
Why opening protection is a business continuity decision
For a business, a broken storefront is rarely just a glass bill. Water and wind entering through one opening can ruin inventory, equipment and records, and keep the doors shut long after power returns. The Insurance Institute for Business and Home Safety (IBHS), in announcing its Commercial Ready: Hurricane guide for small businesses on July 16, 2020, stated that one in four small businesses will not reopen after a natural disaster. That guide is organized into low-cost ways to get ready, improvement projects, and last-minute preparation, and it includes guidance on what to ask a contractor.
The National Institute of Building Sciences' Natural Hazard Mitigation Saves 2019 Report, funded by HUD, is described by NIBS as the most exhaustive benefit-cost analysis of natural hazard mitigation, covering code adoption, exceeding codes and retrofits. It is a useful reference for owners making the case for mitigation to partners or boards.
An openings-focused continuity plan
- Inventory every opening: storefronts, windows, doors, overhead doors, skylights and louvers, with photos and product approval numbers.
- Classify each one: impact rated, protected by a shutter, or unprotected.
- Write the deployment roster for shutters and panels, with backups, and store tools and keys where staff can reach them.
- Set a trigger. FLASH defines a hurricane watch as hurricane conditions possible within the area and a warning as hurricane conditions expected. Many businesses deploy at the watch stage because staff may be unavailable later.
- Protect what is inside: move inventory and electronics away from glass, and back up records off site.
- Plan the restart: contacts for your glazing and shutter contractors, your building department, your insurer and, in Texas coastal counties, TDI's windstorm field office (800-248-6032, option 4).
- Review annually before June 1, the start of the Atlantic hurricane season, which runs through November 30.
See business hurricane preparedness for openings for a longer planning guide.
How long do commercial window replacement projects take?
We could not find a primary-source figure for typical durations, and any single number would mislead. Commercial window projects are custom: products are made to measured sizes, storefront systems need shop drawings, threshold buildings need a special inspection plan, and multi-story work needs access equipment. Ask the engineer and bidders for a written schedule covering:
- Engineering and wind calculations.
- Shop drawings and product approval submittals.
- Permit review, including zoning review for permanent shutters in Miami-Dade.
- Manufacturing after field measurement.
- Mock-up installation and field testing.
- Production installation, phased around business hours and tenants.
- Inspections, special inspector reports and final approval; in Texas coastal counties, TDI or appointed inspector visits during construction and the WPI-8.
Two business points: schedule exterior glass work outside the peak of hurricane season where you can, and require the contractor to have a plan to close openings fast if a storm threatens mid-project. If you need to keep operating, phase the storefront in sections and ask for temporary protection at night. See lead times and hurricane season.
After the storm: price gouging, contractors and repairs
Businesses are buyers after storms too, and the same consumer protections partly apply. Florida section 501.160 makes it unlawful, during a declared state of emergency, to sell or rent essential commodities, including supplies, services, materials and lumber needed because of the emergency, at an unconscionable price within the emergency area; it is enforced by state attorneys and the Florida Department of Legal Affairs. In Texas, the Deceptive Trade Practices Act (Business and Commerce Code 17.46(b)(27)) makes it a deceptive practice to take advantage of a declared disaster by charging an exorbitant or excessive price for building materials, construction tools and other necessities.
Before signing an emergency storefront replacement:
- Verify the Florida license at myfloridalicense.com. Under section 489.127, unlicensed contracting during a governor-declared state of emergency is a third-degree felony.
- Get a written scope with the product approval numbers and design pressures for the replacement glass.
- Confirm who pulls the permit.
- In Texas coastal counties, file the WPI-1 before work starts so the repair can be certified for TWIA coverage, and do not make final payment until the work is done and the certificate is issued, as TDI advises.
See hurricane window scams and storm chasers and hurricane damage claims and repairs.
How to choose a provider
- Confirm the building's Risk Category and design wind speed on the sealed drawings.
- Check whether the site is in the wind-borne debris region or the HVHZ.
- Inventory every opening, including storefronts, overhead doors, skylights and louvers.
- Require current Florida product approvals or Miami-Dade NOAs at the installed size and design pressure.
- Ask whether the building is a threshold building and budget for the 2026 special inspection requirements.
- Verify the contractor's license category fits the building (general or building contractor for commercial glass).
- Write field testing (AAMA 502 or 503) and retest responsibility into the contract.
- For shutters, write a deployment roster and check exits and manual overrides.
- Clarify landlord and tenant duties for glass, shutters and deployment in the lease.
- Ask your agent or broker which opening protection credits your commercial carrier gives and what proof it needs.
- In Texas catastrophe areas, file WPI-1 before work and get the WPI-8 at the end.
- Review the plan every year before June 1.
Related hurricane shutters and impact windows guides
- Florida Building Code Opening Protection Rules: When Is Impact Protection Required?
- What Is the HVHZ? Hurricane Protection Rules in Miami-Dade and Broward vs. the Rest of Florida
- Are Roll-Down Hurricane Shutters Worth It? Motorized vs. Manual, Battery Backup and Power Outages
- What Is a Hurricane-Rated Garage Door? Wind Load vs. Impact Ratings, Bracing Kits and How to Read the Label
- How Should a Business Protect Its Storefront, Doors and Inventory Before a Hurricane?
- What Building Codes Apply to Windows and Shutters on the Texas Coast?
- How Do Condo Buildings Replace All Their Windows? Engineering, SIRS, Votes, Access and Costs in Florida and Texas
- Missile Impact Tests Explained: What Are the Large and Small Missile Tests, ASTM E1996/E1886 and TAS 201/202/203?
Hurricane shutters and impact windows by state and city
Questions people ask
Do commercial buildings in Florida have to have impact windows?
In the wind-borne debris region, glazed openings must be impact resistant or protected by an approved impact-resistant covering under Florida Building Code section 1609.1.2. In Miami-Dade and Broward, section 1626.1 requires the whole building envelope to meet impact criteria or be protected. Shutters are an allowed alternative to impact glass in most cases. Replacement windows and doors on existing commercial buildings must meet Chapter 16 under FBC Existing Building 707.4.
What is Risk Category in the building code?
Risk Category ranks a building by the hazard to people if it fails. Florida Building Code Table 1604.5 puts low-hazard buildings in Category I, most buildings in II, large assembly, schools and similar uses in III, and essential facilities such as hospitals with emergency treatment, fire and police stations and designated shelters in IV. Higher categories get higher design wind speeds, and in the HVHZ, Category IV buildings face a faster large missile test.
Do hospitals and hurricane shelters need stronger opening protection?
Yes. Designated hurricane shelters and hospitals with surgery or emergency treatment are Risk Category IV. In the HVHZ, Florida Building Code section 1626.2.3 fires the large missile at 80 feet per second for Risk Category IV essential facilities instead of 50, and section 1626.3 keeps the large missile test above 30 feet. Outside the HVHZ, Category IV buildings use a separate wind-borne debris map, Figure 1609.3(3).
Can a store use roll-down shutters instead of impact glass?
In most cases, yes. The Florida Building Code allows glazed openings to be protected by impact-resistant coverings, which must be product approved, tested at 1.5 times the design pressure, permanently labeled and installed per their approval. The catch is that shutters protect only when closed, so the business needs someone to deploy them in time, and closed shutters must not block required exits while people are inside.
Do commercial roll-up and overhead doors need to be impact rated?
In wind-borne debris regions, yes. Florida Building Code section 1609.1.2 names ANSI/DASMA 115 as the impact standard for garage doors and rolling doors, and section 1709.5.2.1 covers wind load testing and labeling of sectional and rolling doors. In the Texas windstorm program, TDI says garage doors must be tested to ASTM E330 with glass panels rated to ASTM E1996.
Who designs hurricane protection for a commercial building?
The engineer or architect of record sets the Risk Category, design wind speed, exposure and design pressures on sealed drawings, and products must meet those values. On threshold buildings in Florida, which include buildings over three stories or 50 feet, window and door installations now also need a special inspection plan from the engineer of record and a certified special inspector, under a 2026 binding interpretation reported by Miami-Dade.
What is a building envelope consultant?
A building envelope consultant is a specialist, usually an engineer or architect, hired by the owner to review how the walls, windows, doors, roof and waterproofing work together. On storefront or curtain wall projects they typically review shop drawings, watch mock-ups, witness field tests such as AAMA 503 for curtain walls and storefronts, and inspect sealant and flashing. The role comes from the contract, not a statute, so define the scope in writing.
Does a Texas business on the coast need a windstorm certificate for new windows?
If the building is in a TDI designated catastrophe area and needs wind and hail coverage through TWIA, yes. TDI says commercial structures insured through TWIA must follow its adopted standards, now the 2024 IBC for applications from April 1, 2026. File the WPI-1 before starting work, schedule inspections during construction by a TDI appointed qualified inspector, and get the WPI-8 when done.
Who is responsible for storm shutters in a commercial lease?
No Florida or Texas statute sets a general rule; the lease decides. Check whether the storefront is part of the landlord's shell or the tenant's improvements, who pays for code-required impact glass if glass breaks, who deploys shutters and who is liable if they are not closed. Put names, keys, tools and a shutter layout in writing, and have a real estate attorney review the lease.
Are commercial insurers required to give wind mitigation discounts in Florida?
Florida section 627.0629 requires discounts or credits for wind mitigation, including opening protection, in residential property insurance rate filings. Commercial property credits depend on each insurer's underwriting, so ask your agent or broker what the carrier recognizes. Keep product approval numbers, permit records, photos of labels and the design pressure schedule ready to prove what you installed.
Does a contractor need a special license for commercial impact windows in Florida?
Yes. A general contractor may do any licensed work, and a building contractor may remodel or improve any size building if the work does not affect structural members. A specialty structure contractor may install shutters and other windstorm protective devices without height limits, but its window and door scope is limited to residential Group R buildings up to three stories or 30 feet, so it cannot be the prime contractor for commercial impact glass.
Sources
- Florida Building Code, Building, 8th Ed. (2023), Chapter 16 Structural Design (UpCodes)
- Florida Building Code, Building, 8th Ed. (2023), Chapter 17 Special Inspections and Tests (UpCodes)
- Florida Building Code, Building, 8th Ed. (2023), Chapter 2 Definitions (UpCodes)
- Florida Building Code, Building, 8th Ed. (2023), Chapter 35 Referenced Standards (UpCodes)
- Florida Building Code, Existing Building, 8th Ed. (2023), Chapter 7 (UpCodes)
- Miami-Dade County: Windows, Shutters, Doors and Security Bars permit checklists
- Florida Statutes (2026) s. 553.71, Definitions (threshold building)
- Florida Statutes (2026) s. 553.79, Permits; special inspectors
- Florida Statutes s. 553.842, Product evaluation and approval
- Florida Statutes s. 489.105, Definitions (contractor categories)
- Florida Administrative Code rule 61G4-15.015, Specialty Structure Contractors
- Florida Statutes s. 489.127, Prohibitions; penalties
- Florida Statutes s. 627.0629, Residential property insurance; rate filings
- Florida Statutes s. 501.160, Rental or sale of essential commodities during a declared state of emergency
- City of Tampa Post-Hurricane Permitting Guide (April 2026)
- TDI: Windstorm adopted building codes
- TDI: Windstorm general questions
- TDI: Windstorm inspection process
- TDI: Protecting openings FAQ
- TDI: Making repairs after a storm
- TDI: Completed construction certificates
- Texas Insurance Code ch. 2210
- Texas Business and Commerce Code ch. 17 (DTPA)
- NOAA NCEI: Billion-Dollar Disasters, Texas summary
- IBHS: IBHS releases hurricane preparedness guide for small businesses (July 16, 2020)
- National Institute of Building Sciences: Natural Hazard Mitigation Saves 2019 Report
- Intertek: AAMA 502-12 Field Testing of Newly Installed Fenestration Products
- Cx Associates: AAMA 503 field testing
- FLASH: Hurricane
- Florida Climate Center (FSU): Hurricanes
This guide was written by our editorial team from the public sources listed above. It is general information, not legal advice; confirm licensing and terms directly with any provider.